2 Installation and connection
2-2 Connecting the equipment
BU100RS
34
2.
Run the wires through the terminal block cover (with cable clamp) after removing the
cap of cable clamp for AC output side.
AC input
AC output
Already connected to
AC input terminal block
Output
3.
Connect the L line to L. Connect the N line to N, and connect the G line to G.
Connections to the terminal block shall comply with the standards in Table 1.
G N L G N L
Input terminal
(mounted by default)
(Input surge protection GND)
Output terminal
Table 1
Connectable wire type
Flexible cord
Connectable wire size (copper wire only)
1.25
~
4mm
2
(
AWG16
~
AWG12
)
Recommended cable size
2 mm
2
(AWG14)
L, N, G
Amount of stripped wire
6 to 8 mm
Tightening torque
1.23
±
0.15 N
・
m
Outer diameter of the calbe
φ
6 to 10mm
Recommended ring terminal for the wire
V2-P4 (JST)