B7AM-6BS
B7AM-6BS
54
Operation
Power Supply
The six positive and six negative terminals on the terminal block are internally connected. Use positive and negative terminals for the power
supply terminals and another negative terminal for the negative signal line. Connect the SIG1 terminals to SIG2 terminals for the signal lines.
I/O Delay: Normal Speed
Note:
A VCTF cable with a thickness of 0.75 mm
2
min. must be used for signal transmission.
(12 to 24 V)
(12 to 24 V)
DC Power
supply
DC power
supply
Transmission distance
500 m max.
Set the selector switch to 19.2 ms
Set the selector switch to 19.2 ms
Power supply
Power supply
I/O Delay: High Speed
Note:
A shielded cable with a thickness of 0.75 mm
2
min. must be used for signal transmission. It is recommended that the shield
be grounded.
The maximum transmission distance is 10 m if a VCTF wire with a thickness of 0.75 mm
2
is used instead of a shielded cable
for the transmission path.
Set the selector switch to 3 ms
Set the selector switch to 3 ms
(12 to 24 V)
(12 to 24 V)
DC power
supply
DC power
supply
Power supply
Power supply
Transmission distance
100 m max.