Conductive Level Controller

 61F-GP-N2

3

Connections

Automatic Water Supply and Drainage Control

1.

Water supply

Connect electromagnetic switch coil terminal A to Tb.

The pump stops when the water level reaches E1 and starts when
the water level drops below E2.

2.

Drainage

Connect the electromagnetic switch coil terminal A to Ta.

The pump starts when the water level reaches E1 and stops when
the water level drops below E2.

Note: 1.

The diagram shows the connections for water supply. When
draining, change the connection Tb to Ta.

2.

The earth terminal must be grounded.

Operation

The conductive type level controller consists of a plug-in controller
connected to a set of stainless steel probes. These are cut to length
and inserted vertically into the liquid. A low voltage is applied
between these probes and the earth probe (or tank, if it is electrically
conductive). The water provides a current between the earth probe
and the high-level probe. The output relay in the controller is ener-
gized when the water level reaches the high-level probe and de-ener-
gized when the water level falls below it.

For two-point control a low-level probe is used as well. In this case
the relay does not de-energize until the water level falls below the
low-level probe. Using the low-level probe allows a wide differential
between switching a pump on and off, and can avoid excessive pump
operation during tank emptying or filling. If this differential is not
required, the low-level probe need not be connected. 

Dimensions

Note: Note:

All units are in millimeters unless otherwise indicated.

1

7

E1

E2

6

S1

S2

E3

8

2

3

5

Ta

Tb

Tc

Power source

220 or 
240 VAC

MCCB

Electromagnetic 
switch

Earth

Tank

Stop

Start

Reservoir

 

R S T

4

A

M

P

E1

E2

E3

91

61F-
GP-N2

PF083A

70

84

38

49.4

38

80

70

Summary of Contents for 61F-GP-N2

Page 1: ...maintenance of electrodes When mounting space is limited Special 3 pole holder of small size and light weight Ideal for soft drink vendors etc where only limited space is avail able For low specific l...

Page 2: ...industrial water sewage SUS 304 AISI 304 F03 01 SUS304 1 line F03 02 SUS304 F03 03 SUS304 Purified city water industrial water sewage dilute alka line solution SUS316 AISI 316 F03 01 SUS316 2 lines F...

Page 3: ...between these probes and the earth probe or tank if it is electrically conductive The water provides a current between the earth probe and the high level probe The output relay in the controller is en...

Page 4: ...hree integral 300 mm length electrodes However a type having 1 000 mm length electrodes is available on request Mounting Holes Rubber packing 11 3 l 7 12 32 38 5 PF1 2 Parallel thread Electrode SUS304...

Page 5: ...ds although they may corrode depending upon the temperature and working conditions Note that the Conductive Level Controller 61F GP N2 is capable of controlling liquids with specific resistances of up...

Page 6: ...nance of the product When fitting crimping terminal s to terminal screw s use a tight ening torque of between 0 45 and 0 6 N m Use power supply of appropriate specifications to provide control source...

Page 7: ...r application or use The following are some examples of applications for which particular attention must be given This is not intended to be an exhaustive list of all possible uses of the products nor...

Page 8: ...rs into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 OMRON Corporation Industrial Automation Company Industrial Devices and Components Division H Q Measuring Components...

Reviews: