![background image](http://html1.mh-extra.com/html/omron/3g8b3-srm00/3g8b3-srm00_product-manual_742321006.webp)
C200HW-SRM21-V1
C200HW-SRM21-V1
15
Unit Specifications
Current consumption
150 mA max. at 5 VDC
Number of I/O points
256 points (128 inputs/128 outputs), 128 points (64 inputs/64 outputs) (switchable)
Number of occupied words
256 points: 20 words (8 input words/8 output words, 4 status data)
128 points: 10 words (4 input words/4 output words, 2 status data)
PC
CS1, C200HX (-ZE), C200HG (-ZE), C200HE (-ZE), C200HS
Number of points per node number
8 points
Max. number of Slaves per Master
32
Status data
Communications Error Flag and Active Slave Node (see note)
Weight
200 g max.
Approved standards
UL 508 (E95399), CSA C22.2 No. 142 (LR51460)
Note:
These flags use the AR area.
Ratings
The ratings of the Unit are the same as those of the CS1, C200HX, C200HG, C200HE, and C200HS.
Nomenclature
Indicators
Indicates the operating status of the Master Unit and
the status of communications with the Slaves.
Rotary Switch
This switch sets the Master’s one-digit hexadecimal
unit number.
DIP Switch
These pins have the following functions:
Pin 1:
Max. number of Slaves setting
Pin 2:
Baud rate setting
Pins 3 to 4: Reserved (Always OFF.)
Communications Terminals
Connect the Slaves’ transmission cable to
these terminals.