7. Connection Procedure
7.2.2. Parameter Setting
Set the Inverter parameters.
1
Turn ON the power supply to the
Inverter.
*Set the parameters by using
the digital operator on the front
of the Inverter.
Display
Various parameters, frequency/set
value and other data are
displayed (red).
RUN key
Runs the Inverter. Take note that
this key is enabled only when the
RUN command destination is the
Digital Operator.
STOP/RESET
Key
This key decelerates the Inverter
to a stop. (Although the
STOP/RESET key is enabled
even when a RUN command is
issued to a destination other than
the Digital Operator (factory
default), it can be disabled by a
Setting (b087).)
If the Inverter is already tripped,
the trip will be reset (return from
the tripping).
Mode key
Parameter is displayed: Move to
the beginning of the next function
group.
Data is displayed: Cancel the
setting and return to the
parameter display.
Individual input mode: Move the
blinking digit to the left.
Regardless of the displayed
screen, pressing and holding this
key (for 1 second or more)
displays the data for Output
Frequency Monitor (d001).
Increment key
Decrement key
These keys are used to
increment/decrement a parameter
or set data. Pressing and holding
each key increases the
incrementing/decrementing
speed.
Pressing the Increment and
Decrement keys together
activates the "Individual Input
MODE" where each digit can be
edited independently.
Enter key
Parameter is displayed: Move to
the data display.
Data is displayed: Confirm/store
the setting (in the EEPROM) and
return to the parameter display.
Individual input mode: Move the
blinking digit to the right.
12
Summary of Contents for 3G3MX2 Series