Functions and Procedures
4-4
OMNTEC
®
Mfg., Inc.
4.1.6 Perform
VLD
On-demand VLD testing (Volumetric Leak Detection) can be manually enabled or
disabled by toggling VLD in Screen #3 of the MAIN Menu. The procedure is
provided in
Section 3.2.2.7 – VLD Submenu
.
4.1.7 Enable/Disable
Communications
While remote communication is in effect, access to system controls is inhibited. To
prevent being locked out of system while working, disable communications. Starting
in Screen #1 of the MAIN Menu, do the following:
1. Select MORE (four times) to advance to Screen #5.
2. Select DIAG. The DIAG Submenu (see
Section 3.2.2.12 –DIAG Submenu
) is
displayed.
3. Select E/D to enable or disable communications.
4.1.8
Testing Alarms for Product and Water
Alarms are tested by adjusting the product or water height until alarm is triggered
(see
Section 3.2.2.12 – DIAG Submenu
).
4.1.9 Data
Direction
Choose where data is to be sent (i.e., printer, lcd, etc). The procedure is provided in
Section 3.2.2.13 – PRINTER Submenu
.
4.1.10
Remote Testing of RAS Annunciator
The RAS Annunciator is always tested whenever the
TEST
key is selected on the
controller’s front panel. For remote testing, press and release the horn silence button
on the annunciator itself. Lights will blink and horn will sound on both the controller
and the annunciator.
4.2
Responding to Alarms
The following procedure describes how to respond to alarms and retrieve alarm data.