OEL8000II
Owners Manual
3-21
Procedure for running VLD tests
Before running a VLD test for a specific tank, wait four (4) hours after a delivery to
allow the contents to settle. Also, the tank must remain inactive for about 4.5 hours
while the test is in progress. This assumes the test has been programmed for 4 hours
and the dwell time has been programmed for 0.5 hours.
CAUTION
Failure to comply with recommendations may
result in incorrect data.
1. Select VLD in Screen #3 of the MAIN Menu. The VLD Submenu is displayed
(see Figure 3-20a).
2. Using the keypad, enter a tank number (1 through 8 or enter 0 to select all tanks)
and select ENTER. The test starts and the LCD returns to Screen #1 of the MAIN
Menu.
Note: To exit the VLD Submenu without starting a test, select EXIT. The LCD
return to Screen #1 of the MAIN Menu.
3. If you didn’t choose all tanks (0) in Step 2, you can repeat Steps 1 and 2 for each
additional tank to be tested. A printout will be provided when testing is
completed (see Figure 3-20b).
Note: VLD in Screen #3 functions as a toggle. Selecting it while a VLD test is in
progress will stop the test.
3.2.2.8
DROP E/D Submenu
The DROP E/D Submenu (see Figure 3-21) is entered from Screen #4 of the MAIN
Menu. It permits enabling or disabling the printer to provide an automatic printout
whenever a delivery (DROP) occurs. The system can store drop data for up to five
drops per tank and a maximum of 40 drops for all tanks in the system.
The second line in the LCD indicates that automatic printout can be enabled or
disabled by selecting E or D. The third line indicates the current status. In the
example below, automatic printout is enabled.