In order to reduce the line loss of AC side (no more than 1% of Pout), Omnik suggest that the
length of AC cable from the inverter to the distribution box should not exceed the limit below.
Model
Rated current
Length of cable
6 mm
2
10 mm
2
Omniksol-5k-TL3
21.7A
18m
30m
Omniksol-6k-TL3
26A
15m
25m
1) Strip the cable 12mm
2) Insert the striped cable into cord end terminal and insert the assembly into barrel.
3) Then the line will like the picture below.
4) Insert the finished 3 lines into AC cover assembly with the following sequence
:
5) Open the plastic cover, use slot type screwdriver to press the shrapnel in the indicated
position, and then put the line in the right hole, please note the sequence of the line shall
in the right order: N,L,PE
12mm