29
6.2.2 Assembly Instructions
In order to reduce the line loss of AC side (no more than 1% of Pout), Omnik suggest that the
length of AC cable from the inverter to the distribution box should not exceed the limit below.
(for Omniksol-5k/6k-TL3 please start from section 6.2.2.1)
Model
Rated current
Length of cable
2.5 mm
2
4 mm
2
Omniksol-1k-TL2-M
4.3A
37m
59m
Omniksol-1.5k-TL2-M
6.5A
25m
40m
Model
Rated current
Length of cable
4 mm
2
6 mm
2
Omniksol-2k-TL3-S
10A
30m
/
Omniksol-2.5k-TL3-S
12.5A
24m
/
Omniksol-3k-TL3-S
15A
20m
30m
Model
Rated current
Length of cable
4 mm
2
6 mm
2
Omniksol-3k-TL3
13A
20m
30m
NOTICE
Use
14-12AWG (2.5
– 4 mm
2
)
copper wire for all AC wiring
connections to
Omniksol1k/1.5k-TL2-M
use
12-10AWG (4
– 6 mm
2
)
copper wire for all AC wiring
connections to
Omniksol-2k/2.5k/3k-TL3-S
Use
12-10AWG (4
– 6 mm
2
)
copper wire for all AC wiring
connections to
Omniksol-3k/3.68k/4k-TL3
Use
10-8AWG (6
– 10mm
2
)
copper wire for all AC wiring
connections to
Omniksol-5k/6k-TL3
The above cables use only solid wire or stranded wire.