2. Assembly Instructions
In order to reduce the line loss of AC side (no more than 1% of Pout), Omnik suggest that
the length of AC cable from the inverter to the distribution box should not exceed the limit
below.
Model
Rated current
Length of cable
6 mm
2
Omniksol-10k-TL3
14.5A
53m
Omniksol-13k-TL3
18.8A
41m
1) Remove length y of
N,L,1,2
conductor 35mm(1.38
’’)/
PE
conductor 40mm(1.57
’’)
sheath of AC cable terminal, length x about 14mm(0.55
’’) of the inner wrapper, then
dress the conductor terminals with ferrules or tin soldering.
2) Check that all parts of AC connector are present. Then slide hex nut onto the cable
and insert the cable end through clamp ring.
NOTICE
Use a residual current protective device
(residual
operating current: 300mA)
.
NOTICE
Use
10AWG (6mm
2
)
copper wire for all AC wiring
connections to Omnik inverter. Use only solid wire or
stranded wire.