Section 6. System Programming
6-17
Q 11, L4 Restore Reporting –
Enter the digit for the type of Restore reports to be sent. Program the
actual trouble Restore report code in Submode 2, Question 47, Location 4.
L4
Entry
Send AC
Restore
Send Low
Bat. Restore
Send Zone
Restore
Restore
Follows Loop
0
1
✔
2
✔
3
✔
✔
4
✔
5
✔
✔
6
✔
✔
7
✔
✔
✔
C
✔
✔
D
✔
✔
✔
E
✔
✔
✔
F
✔
✔
✔
✔
Send Zone Restore & Restore Follows
Loop: Normally, zone restores are sent at
bell cutoff, when the panel is disarmed,
and when the panel is reset. If you select
Restore Follows Loop, zone Restore
reports will be sent as soon as the zone
restores.
QUESTION 12 SYSTEM OPTIONS
L1
L2
L3
L4
This question defines various system-wide options.
Q 12, L1 –
Enter the L1 digit for the desired options from the table that follows.
L1
Entry
No Bell
if Dial
Delay
Fast
Zones
5/6
Double-
Balanced
Zones
LED 16/8
Keypads
0
1
✔
2
✔
3
✔
✔
4
✔
5
✔
✔
6
✔
✔
7
✔
✔
✔
8
✔
9
✔
✔
A
✔
✔
B
✔
✔
✔
C
✔
✔
D
✔
✔
✔
E
✔
✔
✔
F
✔
✔
✔
✔
No Bell if Dial Delay: If selected, bell sounding will not
occur until the dialer is activated (bell is delayed by the
same amount of time as the dial delay setting). See
Question 19, Location 4 for setting the dial delay (15–
255 seconds) and Submode 2, Questions 1–24, Location 4
to enable the dial delay for each zone.
Fast Zones 5/6: Sets zones 5 and 6 to fast response
(10mS). If set, these zones must be wired as NC loops
(cannot be double-balanced zones or part of zone
doubling).
Double-Balanced Zones: Select if using double-
balanced zones. This option allows hardwired zones to be
wired such that a tamper will be detected on an open or
a shorted loop.
LED 16/8 Keypads: Select if using 16 LED keypads.
This option informs the system if you are using 16 LED
keypads (L1 entry between 8 and F). If not using LED
keypads or if using 8 LED keypads, this location is set to
off (L1 entry between 0 and 7).