TROUBLESHOOTING COMMUNICATIONS

If a unit fails to report, the following might solve the problem:

FROM MASTER

Insure master is up and running, check to see if other units are reporting.  If no units at all are reporting, reset 
master station computer.  If resetting master station computer has no effect, reset master radio control unit.  If 
no units communicate after this, an equipment failure is possible.   We will use your C3IConfig PDA as a 
master and attach it to the master radio control unit to check status.

If some units will report, then:

Make sure digipeaters are communicating by polling them manually.

g p

g y p

g

y

If digipeater doesn’t report, reset it and insure unit control board and radio equipment is powered.  If it still will 
not report, then connect C3IConfig PDA to check status.

If the digipeater is communicating with the master, try polling the unit with a different digipeater.  It is possible 
that the unit is too far away or has an obstruction reducing the signal strength, etc.  The next step would be to 
try polling it with a path that includes a neighboring gateway ID that responds correctly.  

FROM GATEWAY UNIT

O

G

U

To determine if a gateway has failed, or if the communications path is not reliable, attach the configuration 
PDA.

Check to see if configuration ID matches label’s ID number.

Check to see if utility/segment ID matches system assignment.

Attempt to poll the nearest digipeaters with the PDA and see if data returns.

Document the digipeaters that work reliably with that unit

Document the digipeaters that work reliably with that unit

If the gateway will not communicate with the PDA, check to make sure gateway is powered up.  Next attempt 
to reset the gateway by un-powering then power back up.  If unit still fails, try a different gateway and consult 
Omni-Pro.

Summary of Contents for C3IWirelessGateway

Page 1: ...C3IWirelessGateway Installation Manual Omni Pro Software Inc 23608 458th Avenue Madison SD 57042 C3IWireless Gateway Installation Manual 605 270 2285...

Page 2: ...ys 3 Pilot Relays 2 Meter Encoder Inputs RS485 Serial Port Metering Inputs Integrated VHF Radio Transceiver Power Supply GE I210 C i ti M d l GE I210 Communication Modules Plug In Type 12 Volt Regulat...

Page 3: ...ROM MASTER TO DIGIPEATER ID 20 POLL MESSAGE FROM DIGIPEATER ID 20 TO UNIT ID 500 RESPONSE MESSAGE FROM UNIT ID 500 TO DIGIPEATER ID 20 RESPONSE MESSAGE FROM DIGIPEATER ID 20 TO MASTER COMPUTER RESPONS...

Page 4: ...he digipeater is communicating with the master try polling the unit with a different digipeater It is possible that the unit is too far away or has an obstruction reducing the signal strength etc The...

Page 5: ...ulators Meter Diagnostics and Voltage Remote Disconnect Status Where Available With GE I210 RD Meter Demand Poll C I Units Only 2 Input Counters 2 Input Counters 4 Status Inputs 3 Relay Status 3 Relay...

Page 6: ...N See Picture The condensation facing DOWN See Picture The condensation drain hole is located on the bottom of enclosure Screw Terminals are labeled for power pulse status inputs and relays 1 3 Power...

Page 7: ...arness Gateway should now be operational Verify operation of GREEN power status LED LED will blink continuously on the standard version of the GREEN power status LED LED will blink continuously on the...

Page 8: ...are simply wired to the corresponding terminals on the encoder meter head The register reading must be assigned to one of the 4 input channels on the C3IWireless Gateway The C3IConfig PDA is used to...

Page 9: ...s no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the e...

Reviews: