OMEGA-VSHYe.F-IOM-2108
16
10. MAINTENANCE GUIDE
Proper unit maintenance will result in optimal unit perfor-
mance and prevent potentially costly repairs or property
damage. Turn unit disconnect switch to off and turn unit
off at circuit breaker/fuse panel before starting mainte-
nance procedure.
Do not operate unit without filters or during
any temporary construction that could clog the
air filter or air coil.
Do not use any cleaning solutions that contain
acids on the air
-
refrigerant coil or any refriger-
ant components.
30 DAY MAINTENANCE
1.
Visually inspect filter monthly for dirt and clogging.
Replace as required with a quality filter.
2.
Vacuum dust from unit air grilles and surrounding
coil area with soft bristle brush attachment as re-
quired.
3.
Every month visually inspect unit for any signs of
water leaks, or water damage around floor or sur-
rounding drywall.
3 MONTH MAINTENANCE
1.
Remove ERV filters located at each ERV fan and
wash with water or mild soap.
2.
Inspect condensate drain every 3 months for signs
of stagnant water, microbial growth, and mineral
buildup. Clean drain pan with an appropriate clean-
ing solution as required to prevent condensate hose
blockages and microbial growth.
3.
Check valves and hoses for signs of leaks, cracking
or deterioration.
6 MONTH MAINTENANCE
1.
Remove ERV Core and wash with water or mild
soap.
2.
Check condensate flow to ensure adequate drain-
age and test for signs of impending blockages.
3.
Check that condensate alarm is operating correctly.
Alarm trips whenever water level rises above sen-
sor threshold and locks unit operation.
4.
Visually inspect the air coil for signs of dirt accumu-
lation. Use a mild detergent or coil
-
cleaning agent.
DO NOT use any cleaning solutions that contain an
acid, including acetic acid (vinegar). Damage to the
air coil may occur resulting in possible refrigerant
leaks.
ANNUAL MAINTENANCE
1.
Perform an annual maintenance inspection of the
fan and blower motor assembly. All units come with
permanently lubricated fan motors. DO NOT oil or
lubricate fan motors. Clean up any dirt or debris that
may have accumulated.
2.
Visually inspect the electrical box annually for signs
of component damage due to overheating or poor
electrical contact.
3.
Completely clean the interior of the cabinet. Vacu-
um any dust or debris.
REPLACEMENT FILTERS & REFRIGERANT
CHARGE
Disposable 1
-
inch thick replacement filters can be ob-
tained from most HVAC parts suppliers. See list of filters
sizes below.
Factory provided filters are MERV 10. Pleated filters
rated between MERV 8 to MERV 11 are preferable as
they will provide optimal filtration. Higher rated filters
(MERV 12, 13+) may reduce airflow and affect unit heat-
ing and cooling performance. Installing high efficiency
filters will result in the need to replace filters more fre-
quently.
Filter Sizes
VSHYe 030
VSHYe 040
VSHYe 050
VSHYe 060
VSHYe 080
VSHYe 100
VSHYe 120
Model
Cabinet
Size
Replacement Filter
Size (in)
Y
14 x 25 x 1
16 x 30 x 1
Z
20 x 30 x 1