background image

 

 

 

 

 

                                                     

OMEGA-VSHYe.F-IOM-2108

 

 

 

10

 

 

 

 

 

8. CONTROLS

 

8.1 MICROPROCESSOR CONTROLLER

 

DIP Switch Settings

 

Controller DIP switch contains 6 switches for setting up 
Thermostat,  Fan,  and  System  settings.  Microprocessor 
DIP  settings  are  factory  set  based  on  order  configura-
tion.  Make  changes  if  warranted  by site conditions.  Be-
low are the 6 settings:

 

DIP Switch Settings

 

Heat/Cool Thermostat 

-

 Requires Power to G (Fan)

 

Ensure thermostat provides 24V power to G (fan) termi-
nal during call for heating or cooling. When using HEAT/
COOL  thermostat,  DIP  #1  is  set  to  the 

OFF

” 

position. 

See table below for thermostat connections to controller 
terminal blocks:

 

Thermostat Cable

 

Unit comes with a 24 inch long standard 6

-

wire thermo-

stat cable.  This cable is factory wired to R, G2, G3, Y, 
O/B, C on the controller board terminal strip.  Wire other 
end of pigtails to thermostat harness. A minimum 4

-

wire 

thermostat cable is required for single fan speed thermo-
stats that do not require a common wire connection. See 
Thermostat Wiring Detail.

 

Whisper Mode

 

Whisper mode is factory enabled and runs main blower 
fan  at  pre

-

determined  low  fan  speed  for  continuous  air 

circulation. A jumper is factory installed between 

R

’ 

and 

G1

’ 

terminals on  TB1  of control  board  to enable Whis-

per  mode.  With Whisper  Mode  DIP  Switch  #6  is  set  to 
(ON) Auto. The manual fan speed switch is not used.

 

Single Fan Speed Thermostat

 

If  connecting  thermostats  with  single  fan  speed  control 
connect fan speed to either the G2, or  G3 terminals:

 

G1 = 

Whisper

” 

Mode

 

G2 = MEDIUM fan speed

 

G3 = HIGH fan speed

 

(Do not wire thermostat fan to G1 terminal)

 

Multi Fan Speed Thermostat

 

Up  to  two  fan  speeds  can  be  selected  from  a  multi

-

speed  thermostat.  Connect  two  of  the  thermostat  fan 
speeds to the G2, and G3 terminals:

 

G1 = 

Whisper

” 

Mode

 

G2 = MEDIUM fan speed

 

G3 = HIGH fan speed

 

(Do not wire thermostat fan to G1 terminal)

 

Fan Control with EC Motors (ECM)

 

Low  voltage  PULSE  WIDTH  MODULATED  (PWM)  sig-
nal  is  utilized  to  control  motor  speed  between  0  and 
100%  of  full  speed.  The  controller  has  been  pro-
grammed  to  use  3  pre

-

programmed  speeds  for 

Whisper

” 

Mode, Medium and High. Inside electrical box 

a label indicates the factory pre

-

programmed speed set-

tings.

 

 

8.2 SEQUENCE OF OPERATION

 

Call for Heating and Cooling 

 

Demand  call  for  Heating  or  Cooling  are  initiated  at  the 
thermostat. 

 

Cooling

 

When  a  call  for  COOLING  is  made,  the  auto  shut

-

off 

control  valve  (COAX  Flow  valve)  will  divert  water  flow 
through  coaxial  heat  exchanger.    The  compressor  con-
tactor will then be energized so long as none of the fol-
lowing fault conditions are present:

 

• 

High

-

Pressure Alarm

 

• 

Low

-

Pressure Alarm

 

• 

Condensate Over Flow Alarm (Optional)

 

• 

Compressor  Anti

-

Short  Cycle  7  min.  timer  has  not 

expired

 

• 

Entering Water Temperature exceeds limits.

 

• 

Leaving Water Temperature exceeds limits.

 

 

DIP DESCRIPTION

OFF

ON

1

Tstat Type

Heat/Cool Tstat 

Heat Pump Tstat

2

HP Type

Hybrid HP

3

FlowType

Variable Flow

4

Coax Valve

Coax Valve NC

5

HeatCoil

Heat Coil Valve NC

6

FanMode

Fan Auto

NO =  Normally Open and NC = Normall Closed

DIP 1 (ON or OFF) = HEAT/COOL Thermostat

TERMINAL 

BLOCK

WIRE

DESCRIPTION

TB1-4

R

24VAC – Line – (R)

TB1-3

G1

Whisper Mode

TB1-2

G2

Medium Speed Fan

TB1-3

G3

High Speed Fan

TB2-3

Y

Call for Cooling

TB2-2

O/B

"W" Call for Heating

TB2-1

C

Common (Optional)

Summary of Contents for VSHYe Series

Page 1: ...IOM VERTICAL STACKED HYBRID HEATING COOLING W INTEGRATED ERV HIGH EFFICIENCY HE MODEL VSHYe DEV F DOCUMENT RELEASE OMEGA VSHYe F IOM 2108 3325A Orlando Dr Mississauga ON L4V 1C5 T 905 670 2269 omega h...

Page 2: ...re 7 Cooling Season 7 Heating Season 7 Operating Limits 7 6 Chassis Installation 8 Installation of Fittings and Hoses 8 Chassis Install 8 7 Unit Start Up 9 Checklist 9 Initial Start Up 9 8 Controls 10...

Page 3: ...result in death of serious injury ALL FIELD WIRING MUST BE PER FORMED ONLY BY A QUALIFIED ELECTRICIAN All wiring must be in accord ance of with the manufacturer s specifications Wiring that is improp...

Page 4: ...x 8 8 x 14 10 x 14 12 x 12 VSHYe 050 1 1 4 14 x 8 8 x 14 10 x 16 14 x 12 VSHYe 060 1 1 2 14 x 8 8 x 14 10 x 16 14 x 12 VSHYe 080 2 18 x 8 8 x 18 14 x 18 14 x 14 VSHYe 100 2 1 2 18 x 8 8 x 18 14 x 20 1...

Page 5: ...e furnished with type L M copper Available 3 inch deep swage connections on same size piping Contractor to provide couplings where the piping is not swaged or for joining dissimilar piping sizes Use f...

Page 6: ...k Side Top with 1 1 2 duct flange 3 ERV Ports Bathroom Exhaust Exhaust Air Outside Air 4 Removable ERV core 5 Chassis HP shown 6 Chassis service cover panel 7 1 air filter 8 Acoustic return air R A pa...

Page 7: ...on nect switch The panel is removed by swinging out and lifting it off the support pegs The middle panel is a removable swing panel for ac cessing and servicing the ERV core sensors and fans The upper...

Page 8: ...o not allow stub outs to rest or contact the sheet metal opening Do not allow the risers to bottom out when installing into the swage FOR SHIPPED LOOSE RISER SHUT OFF VALVES Visually inspect riser stu...

Page 9: ...ubbles 3 Shut off the circulating pump and open all the drains and vents to completely drain the system 4 The riser system should be cleaned after the initial flush and flushed a second time to adequa...

Page 10: ...e Check chassis nameplate to verify chassis model matches cabinet model for compatibility 2 Align chassis with front of the cabinet and tilt chassis so that the back aligns with the cabinet rails 3 Sl...

Page 11: ...and condensate riser ___All ductwork and ERV connections are complete ___Clean filters are installed ___All cutting sanding drywalling patching work is complete ___Unit blower spins freely ___Thermost...

Page 12: ...fan speed Do not wire thermostat fan to G1 terminal Multi Fan Speed Thermostat Up to two fan speeds can be selected from a multi speed thermostat Connect two of the thermostat fan speeds to the G2 and...

Page 13: ...ts anytime a fan and compressor request are made to develop flow in the water coil Valve Closed Timer The valve closed timer of 1 minutes starts anytime a call for compressor is terminated to allow fo...

Page 14: ...lows ensure maximum efficiency The exhaust air fans should be calibrated on site during start up and commissioning for both high speed mode P1 and low speed mode P2 Use the ERV board mounted low LO SP...

Page 15: ...00 0 025 0 05 0 075 0 10 0 15 0 20 0 25 0 30 0 40 0 50 25 Speed 6 Watts 10 O clock 43 34 28 22 18 12 37 Speed 13 Watts 11 O clock 70 54 43 34 27 15 7 45 Speed 18 Watts 12 O clock 85 67 55 44 35 23 15...

Page 16: ...en up your internet browser i e Explorer Google Chrome and type in the following address 192 168 0 99 Direct to Laptop Method 1 To connect to the controller you will need the follow ing Ethernet cable...

Page 17: ...troubleshooting aid For example in the figure below the first line item indicates Y terminal was ener gized Y 1 when the Cooling CLG 1 and tripped on Low Pressure fault LP 0 Captured unit controller d...

Page 18: ...equate drain age and test for signs of impending blockages 3 Check that condensate alarm is operating correctly Alarm trips whenever water level rises above sen sor threshold and locks unit operation...

Page 19: ...oo cold Adjust Supply Loop temperature higher Cooling Inadequate GPM If auto shut off valve is installed check that control valve actuator opens during call for Heating Set valve to manual mode and re...

Page 20: ...Trips Red Blinking Low pressure alarm Soft Lock Out Red Solid Water loop discharge temperature too hot Non latching alarm Red Blinking Sensor open missing or close shorted Non latching alarm replace...

Page 21: ...s determined by facing front of the unit return air opening Riser Handing Configurations S Supply Riser C Condensate Riser R Return Riser 12 Typ 8 Typ 8 Typ S R Chassis 6 2 2 S R c R S Chassis 2 2 D...

Page 22: ...earance Height Slab Thickness 2 inch overlap Rounded up to 120 or 144 Omega supplies two standard riser lengths 120 10 and 144 12 to be field cut on site Omega does not supply extension tailpieces or...

Page 23: ...RA panels with supply grille apply gasket tape to supply grille throat to insert into unit sup ply discharge flange Acoustic ERV RA Panel Dimensional Drawing Acoustic ERV RA Panel Sizes A B C VSHYe 03...

Page 24: ...Cabinet Base Height Min 5 1 increments B BH G 1 Note Include flooring thickness underlayment and any concrete leveling as part of calculation Example If using a 6 baseboard with 1 Finished Flooring h...

Page 25: ...A OA BE OA BE 8 R S C EA Furring Covers A4 B4 C4 D4 Configurations A1 B1 C1 D1 are Mirrored Furring Covers A2 B2 C2 D2 Configurations A3 B3 C3 D3 are Mirrored A2 Shown A4 Shown Typ min 1 2 Screws x 6...

Page 26: ...ht from Base of Cabinet B 1 D Rough In Height from Base of Cabinet B 2 NOTES Center vertically and horizontally RA panel supply opening with unit front knockout supply discharge For optional RA panels...

Page 27: ...OMEGA VSHYe F IOM 2108 25 VHSYe Electrical Schematic ECM Fan...

Page 28: ...nce ECM w Whisper Mode Factory 6 Wire Thermostat Harness Whip Thermostat Wiring Detail Factory supplied 6 wire thermostat cable shown Whisper Mode standard on VSHYe units Jumper between R and G1 facto...

Page 29: ...0 1140 1120 1100 External Static Pressure in w g 900 750 600 450 375 300 220 1200 1010 820 630 530 460 350 Unit Size EC Motor Speed Minimum SCFM Rated SCFM 030 050 040 080 060 120 100 Note All airflow...

Page 30: ...cing valve see name plate for GPM rating Air Temperature Measure the difference in tem perature across air coil for measuring sensible capacity T LAT EAT Sensible Capacity Btuh T x CFM x 1 08 Entering...

Page 31: ...ctory Set confirm that settings have not been adjusted to non standard settings SW1 ERV Board Power Switch Set to ON ____ Yes No SW2 ERV Toggle Switch Set to Neutral Middle Position _____ Yes No Fan E...

Reviews: