4. Return the meter selector switch to the “RUN” position. This action prompts
the microprocessor to store the set value in memory and deactivates the
potentiometer.
5. Apply pressure to the transmitter that represents the full-scale calibration.
6. Place the meter selector switch in the “S” (Span) position.
7. Adjust the potentiometer until the indicator displays the desired value (
“Potentiometer Adjustment” on Page 3-4).
8. Return the meter selection switch to the RUN position.
9. Select the appropriate adhesive label and apply it to the indicator face directly
above the LCD, as shown in Figure 7-2 on Page 7-4. The local indicator is
supplied with adhesive labels of common engineering units for pressure and
level. Several blank labels have also been provided to allow you to create
individualized engineering units if desired.