4-2
EN
FIGURE 4-1. Installation Flowchart.
High voltage that may be present on leads could cause electrical shock:
• Avoid contact with leads and terminals.
Check for Leaks
(Process
Connections)
Zero Trim
Transmitter for
Mounting Effects
No
B
Yes
A
Yes
No
Check Jumper
or Switches
(Smart Only)
Wire
Transmitter
Power
Transmitter
Zero
Transmitter
DONE
Repeat Steps
until
Calibrated
Mount
Transmitter
Apply Pressure
Refer to
Troubleshooting
Section
Within
Specifications?
VERIFY
START HERE
Bench
Calibration?
FIELD
INSTALL
A
B
Smart
Analog
Set Output Type
Check Configuration
(See Chapter 2)
A
Set Range Points
Set Units
(See Chapter 2)
Set Damping
Analog
Smart
Confirm Transmitter
Configuration
Within
Specifications?
Yes
A
No
Check Configuration
(See Chapter 3)
Within
Specifications?
Yes
A
No
ADJUST ANALOG
ZERO/SPAN
(See Chapter 3)
Perform Sensor
and/or Output
Trim
4690.bk : 4690.s4 Page 2 Tuesday, May 26, 1998 5:28 PM