Scaling
Here you can scale the analog output to correspond to the process reading value.
4-20 mA Example:
This table shows analog output values you should expect if you set 4mA = 0°F
and 20mA = 1000°F
Process Reading
Analog Output Value
0°F
4.00 mA
250°F
8.00 mA
500°F
12.00 mA
750°F
16.00 mA
1000°F
20.00 mA
0-10 Vdc Example:
This table shows analog output values you should expect if you set 0.0Vdc = 0°F
and 10.0 Vdc = 1000°F
Process Reading
Analog Output Value
0°F
0.00 Vdc
250°F
2.50 Vdc
500°F
5.00 Vdc
750°F
7.50 Vdc
1000°F
10.00 Vdc