34
LVCN414-SW Appendix
(continued)
Section Six
SWITCH HYSTERESIS/DEAD BAND
This feature allows you to select a hysteresis or dead band for the
remaining high and/or low alarms.
o
Options for Hysteresis/Dead band
– No Hysteresis, ¼”, ½”,
1”, 2”, ½ cm, 1cm, 2 cm, 5 cm or Not Applicable.
o
High Alarms
– Relay activates above the set point. Relay will
deactivate when the level goes below the set point plus the
value of the hysteresis.
o
Low Alarms
– Relay activates below the set point. Relay will
deactivate when the level goes above the set point plus the
value of the hysteresis.
High Alarm w/ Hysteresis
Low Alarm w/ Hysteresis
Note:
Right click on any item to open the help menu.
Note:
To reset the configuration table, press the Clear Screen button