INSTALLATION

 

(continued)

 

Step

 

Six

 

Fitting

 

Selection:

 

 

Check

 

the

 

part

 

number

 

to

 

determine

 

the

 

required

 

fitting

 

mount

 

size

 

and

 

thread

 

type.

  

LVU2800

 

Series

 

is

 

commonly

 

installed

 

in

 

tank

 

adapters,

 

flanges,

 

brackets

 

or

 

standpipes.

  

Note:

 

Always

 

include

 

the

 

gasket

 

when

 

installing

 

the

 

LVU2800

 

Series.

  

1.

 

Tank

 

Adapter:

  

Select

 

a

 

tank

 

adapter

 

fitting,

 

such

 

as

 

a

 

1”

 

adapter

 

for

 

the

 

LVU2810

 

series

 

or

 

a

 

2”

 

adapter

 

for

 

the

 

LVU2818,

 

LVU2826

 

&

 

LVU2832

 

series.

   

a.

 

For

 

best

 

results,

 

select

 

a

 

2”

 

tank

 

adapter

 

and

 

add

 

a

 

2”

 

x

 

1”

 

reducer

  

bushing.

   

b.

 

Avoid

 

tank

 

adapter

 

(thread

 

x

 

thread)

 

styles

 

and/or

 

pipe

 

stops

 

forward

 

of

 

the

 

installed

 

transducer.

 

c.

 

Always

 

mount

 

the

 

tank

 

adapter

 

so

 

the

 

majority

 

of

 

fitting

 

is

 

outside

 

the

 

tank.

 

i.

 

Never

 

mount

 

the

 

tank

 

adapter

 

upside

 

down

 

or

 

the

 

bulk

 

of

 

the

 

material

 

is

 

inside

 

the

 

tank.

 

 

2”

 

Tank

 

Adapter

 

Socket

 

x

 

Thread

 

Tank

 

Adapter

 

w/

 

2”x1”

 

Reducer

 

Bushing

 

Tank

 

Adapter

 

Thread

 

x

 

Thread

 

 

Do

 

not

 

use

 

thread

 

x

 

thread

 

 

 

 

2.

 

Riser:

 

 

Installations

 

with

 

tall,

 

narrow

 

risers

 

can

 

impede

 

the

 

acoustic

 

signal.

  

a.

 

LVU2818,

 

LVU2826

 

&

 

LVU2832

 

Series:

 

2”

 

(5

 

cm)

 

diameter

 

risers

 

should

 

be

 

no

 

taller

 

than

 

5”

 

(12.7

 

cm).

  

Larger

 

diameter

 

risers

 

should

 

be

 

no

 

taller

 

than

 

12”

 

(30.5

 

cm).

 

b.

 

LVU2810

 

Series:

 

 

 

 

Note:

 

Do

 

not

 

exceed

 

the

 

dimensions

 

listed

 

above

 

 

 

 

Summary of Contents for LVU2800 Series

Page 1: ...LVU2800 Series Ultrasonic Level Transmitter...

Page 2: ...2 of 23...

Page 3: ...il Safe Hold Last Empty Full 21 mA 22 mA Easy to reverse mA output 4 20 mA to 20 4 mA Increased output filtering Table of Contents Introduction 3 Specifications 4 Dimensions 4 About this manual 5 Wiri...

Page 4: ...Feet m or percent Supply voltage 12 28 VDC Loop resist 500 Ohms 24 VDC Signal output 4 20 mA two wire Signal invert 4 20 mA 20 4 mA Signal fail safe 4mA 20 mA 21 mA 22 mA hold last Process temp F 4 t...

Page 5: ...he transducer is made of Polyvinylidene Fluoride PVDF Make sure that the model which you have selected is chemically compatible with the application media Enclosure While the switch housing is liquid...

Page 6: ...sure that all electrical wiring of the switch is in accordance with applicable codes Components LVU2800 Series is offered in three different models Depending on the model purchased you may or may not...

Page 7: ...review of wiring the LVU2800 Series to common display controllers and PLC s Proportional Level Controller LVCN 51 Series JWA mode Factory Setting Proportional Level Controller LVCN 51 Series JWB mode...

Page 8: ...sor materials must be chemically compatible with the liquids to be measured Design a fail safe system for possible sensor and or power failure Never use the sensor in environments classified as Hazard...

Page 9: ...played approximately 5 seconds The MENU items will rotate through display press SELECT to change an item Many UNITS of measurement In the MENU mode press SELECT when UNITS is display then select INCHE...

Page 10: ...height of the liquid from the bottom of the tank o REV MA Allows the transmitter to reverse the current output such that 4 mA is at FULL and 20 mA is at EMPTY o Press Exit to return to the Top level...

Page 11: ...ng the level of liquid in Percent Omega Engineering recommends that when selecting PERCENT configure the HEIGHT and FILL H settings before selecting PERCENT in order to span the LVU2800 Series for you...

Page 12: ...e AIR mode Will display the distance from the bottom of the sensor to the surface of the liquid LIQUID mode Will display the height of liquid measured from the bottom of the tank How to change the dis...

Page 13: ...ss and hold SELECT Approximately 2 seconds until SAVED is displayed 5 When FILL H appears press SELECT 6 Using the UP and DOWN buttons set the Fill Height FILL H to the maximum fill height of the liqu...

Page 14: ...ppears press SELECT 3 When REV appears press SELECT 4 When EXIT appears press SELECT return to Top Level Menu LVU2800 Series is now in the Reverse mode To switch back to the Normal mode follow the ins...

Page 15: ...vel Menu How to set using Target Calibration Full Instead of measuring for Full tank the Full distance can be set automatically This method requires that the tank be Full or at the level that is consi...

Page 16: ...m 6 Avoid mounting in the center of a dome top tank 7 In cone bottom tank position the sensor over the deepest part of the tank Do not install at angle relative to the liquid Do not install within 3 o...

Page 17: ...educer bushing b Avoid tank adapter thread x thread styles and or pipe stops forward of the installed transducer c Always mount the tank adapter so the majority of fitting is outside the tank i Never...

Page 18: ...he plane of the flange such as the Banjo 1 Poly ANSI Flange series AF100 c Use a flange with a 2 thread and add a 2 to 1 reducer bushing to complete the installation 2 Flange w thread out of plane 2 F...

Page 19: ...er bushing to attach the LVU2800 Series to the pipe i With the LVU2810 series be sure to use a plastic reducing bushing 2 Thread x 1 Thread fitting or 2 Slip x 1 Thread fitting d The pipe length shoul...

Page 20: ...onfiguration back to the original factory settings Follow the instructions below to reset LVU2800 Series 1 From the main MENU level press SELECT when VALUES appears 2 When RESET appears press the SELE...

Page 21: ...sound pulses are not reaching the transducer First cycle power off and on waiting 5 seconds between the off and on states If problem persists check the installation fitting against the Installation in...

Page 22: ...22 of 23...

Page 23: ...23 of 23 M 5127 0312...

Reviews: