INSTALLATION

 

Step

 

Six

 

The

 

LVU2800

 

Series

 

should

 

always

 

be

 

mounted

 

perpendicular

 

to

 

the

 

liquid

 

surface

 

and

 

installed

 

using

 

the

 

provided

 

FKM

 

mounting

 

gasket.

  

Make

 

sure

 

that

 

the

 

fitting

 

and

 

transmitter

 

threads

 

are

 

not

 

damaged

 

or

 

worn.

  

Always

 

hand

tighten

 

the

 

transmitter

 

within

 

the

 

fitting.

  

Perform

 

an

 

installed

 

leak

 

test

 

under

 

normal

 

process

 

conditions

 

prior

 

to

 

system

 

start

 

up.

  

Note:

 

The

 

preferred

 

mounting

 

fitting

 

for

 

the

 

LVU2810

 

series

 

is

 

a

 

plastic

 

2”

 

thread

 

(or

 

slip)

  

x

 

1”

 

thread

 

reducer

 

bushing.

 

Mounting

 

Guide

 

1.

 

Do

 

not

 

mount

 

at

 

an

 

angle

 

2.

 

Liquid

 

should

 

never

 

enter

 

the

 

dead

 

band

 

3.

 

Side

 

Wall:

 

a.

 

For

 

LVU2810

 

Series

 ‐ 

mount

 

at

 

least

 

2”

 

from

 

the

 

side

 

wall

 

b.

 

For

 

LVU2818,

 

LVU2826

 

&

 

LVU2832

 

Series

 ‐ 

mount

 

at

 

least

 

3”

 

from

 

the

 

side

 

wall

 

4.

 

Do

 

not

 

mount

 

where

 

obstacles

 

will

 

intrude

 

on

 

sensor’s

 

beam

 

width

 

a.

 

See

 

Specifications

 

on

 

page

 

3

 

5.

 

Do

 

not

 

mount

 

in

 

a

 

vacuum

 

6.

 

Avoid

 

mounting

 

in

 

the

 

center

 

of

 

a

 

dome

 

top

 

tank.

 

7.

 

In

 

cone

 

bottom

 

tank,

 

position

 

the

 

sensor

 

over

 

the

 

deepest

 

part

 

of

 

the

 

tank.

 

 

Do

 

not

 

install

 

at

 

angle

 

relative

 

to

 

the

 

liquid.

 

Do

 

not

 

install

 

within

 

3”

 

of

 

tank

 

sidewall.

 

Do

 

not

 

install

 

with

 

objects

 

in

 

the

 

beam.

 

Do

 

not

 

install

 

in

 

applications

 

with

 

vacuum.

 

 

Installation

 

in

 

existing

 

fittings

 

If

 

the

 

existing

 

fitting

 

is

 

larger

 

than

 

the

 

threads

 

of

 

the

 

LVU2800

 

Series,

 

select

 

a

 

reducer

 

bushing

 

such

 

as

 

a

 

2”

 

thread

 

x

 

1”

 

thread,

 

a

 

2”

 

slip

 

x

 

1”

 

thread,

  

3”

 

thread

 

x

 

2”

 

thread

 

or

 

3”

 

slip

 

x

 

2”

 

thread.

 

Metal

 

Tanks

 

(LVU2810

 

series

 

only)

 

Omega

 

Engineering

 

ultrasonic

 

transmitters

 

have

 

been

 

optimized

 

for

 

use

 

in

 

non

metallic

 

fittings.

   

1.

 

For

 

best

 

performance,

 

avoid

 

the

 

use

 

of

 

metallic

 

fittings.

   

a.

 

Use

 

a

 

plastic

 

2”

 

x

 

1”

 

reducer

 

bushing,

 

or

 

a

 

plastic

 

1”

 

flange

 

(See

 

Fitting

 

Selection

 

on

 

next

 

page).

 

2.

 

While

 

installations

 

directly

 

into

 

a

 

1”

 

metal

 

fitting

 

are

 

not

 

recommended,

 

acceptable

 

results

 

may

 

be

 

obtained

 

if

 

the

 

1”

 

fitting

 

is

 

a

 

half

 

coupling

 

in

 

form

 

and

 

the

 

outer

 

diameter

 

of

 

the

 

coupling

 

is

 

tightly

 

wrapped

 

in

 

vinyl

 

tape

 

to

 

dampen

 

vibrations.

 

 

Summary of Contents for LVU2800 Series

Page 1: ...LVU2800 Series Ultrasonic Level Transmitter...

Page 2: ...2 of 23...

Page 3: ...il Safe Hold Last Empty Full 21 mA 22 mA Easy to reverse mA output 4 20 mA to 20 4 mA Increased output filtering Table of Contents Introduction 3 Specifications 4 Dimensions 4 About this manual 5 Wiri...

Page 4: ...Feet m or percent Supply voltage 12 28 VDC Loop resist 500 Ohms 24 VDC Signal output 4 20 mA two wire Signal invert 4 20 mA 20 4 mA Signal fail safe 4mA 20 mA 21 mA 22 mA hold last Process temp F 4 t...

Page 5: ...he transducer is made of Polyvinylidene Fluoride PVDF Make sure that the model which you have selected is chemically compatible with the application media Enclosure While the switch housing is liquid...

Page 6: ...sure that all electrical wiring of the switch is in accordance with applicable codes Components LVU2800 Series is offered in three different models Depending on the model purchased you may or may not...

Page 7: ...review of wiring the LVU2800 Series to common display controllers and PLC s Proportional Level Controller LVCN 51 Series JWA mode Factory Setting Proportional Level Controller LVCN 51 Series JWB mode...

Page 8: ...sor materials must be chemically compatible with the liquids to be measured Design a fail safe system for possible sensor and or power failure Never use the sensor in environments classified as Hazard...

Page 9: ...played approximately 5 seconds The MENU items will rotate through display press SELECT to change an item Many UNITS of measurement In the MENU mode press SELECT when UNITS is display then select INCHE...

Page 10: ...height of the liquid from the bottom of the tank o REV MA Allows the transmitter to reverse the current output such that 4 mA is at FULL and 20 mA is at EMPTY o Press Exit to return to the Top level...

Page 11: ...ng the level of liquid in Percent Omega Engineering recommends that when selecting PERCENT configure the HEIGHT and FILL H settings before selecting PERCENT in order to span the LVU2800 Series for you...

Page 12: ...e AIR mode Will display the distance from the bottom of the sensor to the surface of the liquid LIQUID mode Will display the height of liquid measured from the bottom of the tank How to change the dis...

Page 13: ...ss and hold SELECT Approximately 2 seconds until SAVED is displayed 5 When FILL H appears press SELECT 6 Using the UP and DOWN buttons set the Fill Height FILL H to the maximum fill height of the liqu...

Page 14: ...ppears press SELECT 3 When REV appears press SELECT 4 When EXIT appears press SELECT return to Top Level Menu LVU2800 Series is now in the Reverse mode To switch back to the Normal mode follow the ins...

Page 15: ...vel Menu How to set using Target Calibration Full Instead of measuring for Full tank the Full distance can be set automatically This method requires that the tank be Full or at the level that is consi...

Page 16: ...m 6 Avoid mounting in the center of a dome top tank 7 In cone bottom tank position the sensor over the deepest part of the tank Do not install at angle relative to the liquid Do not install within 3 o...

Page 17: ...educer bushing b Avoid tank adapter thread x thread styles and or pipe stops forward of the installed transducer c Always mount the tank adapter so the majority of fitting is outside the tank i Never...

Page 18: ...he plane of the flange such as the Banjo 1 Poly ANSI Flange series AF100 c Use a flange with a 2 thread and add a 2 to 1 reducer bushing to complete the installation 2 Flange w thread out of plane 2 F...

Page 19: ...er bushing to attach the LVU2800 Series to the pipe i With the LVU2810 series be sure to use a plastic reducing bushing 2 Thread x 1 Thread fitting or 2 Slip x 1 Thread fitting d The pipe length shoul...

Page 20: ...onfiguration back to the original factory settings Follow the instructions below to reset LVU2800 Series 1 From the main MENU level press SELECT when VALUES appears 2 When RESET appears press the SELE...

Page 21: ...sound pulses are not reaching the transducer First cycle power off and on waiting 5 seconds between the off and on states If problem persists check the installation fitting against the Installation in...

Page 22: ...22 of 23...

Page 23: ...23 of 23 M 5127 0312...

Reviews: