13
of
23
GETTING
STARTED
(continued)
Step
Five
How
to
configure
the
Operational
range
of
LVU2800
Series:
No
cumbersome
measurement
is
required
via
Target
Calibration
to
establish
set
points.
Set
point
distances
are
relative
to
the
tank
bottom.
1.
In
MENU
mode,
select
the
TANK
item.
2.
When
HEIGHT
appears,
press
SELECT
.
3.
Using
the
UP
and
DOWN
buttons,
set
the
HEIGHT
of
the
tank
from
the
transducer
face
to
the
bottom
of
the
tank.
4.
To
enter
the
value,
press
and
hold
SELECT
(Approximately
2
seconds)
until
SAVED
is
displayed.
5.
When
FILL
‐
H
appears,
press
SELECT
.
6.
Using
the
UP
and
DOWN
buttons,
set
the
Fill
Height
(
FILL
‐
H
)
to
the
maximum
fill
height
of
the
liquid
from
the
bottom
of
the
tank.
7.
Press
and
hold
SELECT
(2
seconds)
to
enter
the
value.
8.
When
EXIT
appears,
press
SELECT
return
to
Top
Level
Menu.
Sensor
Height
Fill
‐
Height
Note:
Omega
Engineering
recommends
that
when
selecting
PERCENT,
configure
the
Height
and
Fill
‐
H
settings
before
selecting
PERCENT
in
order
to
span
the
LVU2800
Series
for
your
application
requirements.
When
PERCENT
is
selected,
the
TANK
settings
(Height
and
Fill
‐
H)
will
be
disabled.