14
of
23
GETTING
STARTED
(continued)
Step
Five
How
to
set
a
Reverse
the
Current
Output:
The
default
for
LVU2800
Series
is
to
have
4
mA
at
Empty
and
20
mA
at
Full.
This
is
the
normal
(
NORM
)
setting.
The
output
can
be
reversed
(
REV
)
with
20
mA
at
Empty
and
4
mA
at
Full.
1.
In
MENU
mode,
select
the
TANK
item.
2.
When
REV
MA
appears,
press
SELECT
.
3.
When
REV
appears,
press
SELECT
.
4.
When
EXIT
appears,
press
SELECT
return
to
Top
Level
Menu.
LVU2800
Series
is
now
in
the
Reverse
mode.
To
switch
back
to
the
Normal
mode,
follow
the
instructions
above
and
select
NORM
under
step
3.
How
to
set
the
SAFE
setting:
The
default
for
Fail
‐
Safety
(LOST)
can
be
preset.
The
choices
are
4
mA
,
20
mA
,
21
mA
,
22
mA
and
HOLD
.
1.
In
MENU
mode,
select
the
SAFE
item.
2.
When
the
required
setting
appears,
press
SELECT
.
3.
When
EXIT
appears,
press
SELECT
return
to
Top
Level
Menu.