ALARM 2 ENABLE/DISABLE SUBMENU:
Press
d
5)
Display flashes previous selection. Press
b
until
ENBL
displays to use Alarm 2.
Press
d
6)
Display shows
STRD
stored message momentarily and then
advances to
ABSo
only if it was changed, otherwise press
a
to
advance to
ABSo
Absolute/Deviation Submenu.
If
DSBL
Alarm 2
Disabled
was selected, all submenus of Alarm
2 will be skipped and meter advances to
LOOP
Loop Break
Time Menu. If
ENBL
Alarm 2
Enabled
was selected, Output 2
will automatically
Disabled
, and reassigned as Alarm 2.
The remaining Alarm 2 menu items are identical to Alarm 1 Menu.
Modifying Alarm Settings will not reset the instrument.
3.2.9 Loop Break Time
Figure 3.8 Flow Chart for Loop Break Time
ENTER LOOP BREAK TIME MENU:
Press
a
1)
Press
a
, if necessary, until
CNFG
prompt appears.
Press
d
2)
Display advances to
INPT
Input Menu.
Press
a
3)
Press
a
, if necessary, until Display advances to
LOOP
Loop
Break Time Menu.
Press
d
4)
Display advances to Loop Break Time
ENBL
Enable or
DSBL
Disable Submenu and flashes the previous selection.
LOOP BREAK ENABLE/DISABLE SUBMENU:
Press
b
5)
Scroll through the available selections:
ENBL
or
DSBL
.
Press
d
6)
Display shows
STRD
stored message momentarily and then
advances to
B.TIM
Loop Break Time Value Submenu.
Loop Break is an additional safety feature intended to monitor the rate of change
of the process value, while approaching the SP1. It is strictly intended as an
additional warning system, therefore its use is entirely optional. An active Loop
Break will cause the Process Value digits to blink in a rotating pattern. If the
process value reaches the set point the blinking will stop and
B.TIM
is completed
successfully, otherwise
BR.AL
Break Alarm warning will flash, and Output 1 will
be turned off.