Omega FP-5070 Series Flow Sensors

2

3.  Installation

•  The sensor may be installed in any position, although horizontal 

flow is recommended (the sensor mounted upright). If the 

sensor is not installed upright, the linearity error may be greater 

in the lower part of the sensor's measurement range.

•  Mounting tabs are provided using M4 or #8 self-tapping screws 

(customer supplied). See Dimensions illustration for mounting 

tab hole pattern specifications.

• 

Install sensor with the arrow pointing in the direction of flow.

•  Always maximize distance between the sensor and pump 

source. Never install immediately downstream of valves, 

Installation Hints

• 

Avoid vibrations and shocks.

• 

Avoid solids in the fluid.

• 

Install a filter or line strainer upstream to protect sensor.

1

2

Sensor 
Ground
(silver wire)

Sensor Power:

5 to 24 VDC

(black wire)

Sensor Signal Output
(Red wire)

Max cable length:

300 m (1000 ft)

Sensor 
Plug (side)

Disregard ground 
symbol on connector

95 mm (3.74 in.)

FLOW

65 mm

(2.6 in.)

68 mm (2.7 in.)

Mounting tabs (3),

#8 or M4 self-tapping

screws required

(customer supplied)

32.5 mm (1.28 in.)

bolt circle

4.  Wiring Details

4.1  Cable Extensions

The standard 25 foot sensor cable can be extended to 300 m 

(1000 ft) using 2-conductor shielded twisted-pair cable.

•  Always maintain cable shield through cable splice.

•  For splice-free cable replacement up to 300 m (1000 ft), refer 

to the sensor plug connection diagram (below) for connection 

details.

FLOW 

100 to 150 mm (4 to 6 in.)

100 to 150 mm (4 to 6 in.)

FLOW 

Pipe Fitting 

Adapters  

(included) 

Hand  

tighten 

only! 

Female TxT  

coupling 

 

Female TxT  

coupling 

 

Female TxT  

union 

 

Hose  

adapter 

Compatible pipe/tubing connections (customer supplied): 

Female SxT  

coupling 

 

Coupling 

Pipe or 

tubing

Mounting 

tabs (3)

Dimensions:

fittings, etc. For optimum performance, a straight flow run of at 

least 100 mm to 150 mm (4 to 6 in.) should be provided before 

and after the sensor.

• 

Two pipe fitting adapters (included) convert the G 1/4 in. 

straight threads to 1/4 in. NPT pipe threads. 

Hand tighten 

only!

 Apply 1-2 turns of PTFE sealing tape to all threaded 

connections to prevent leaks.

CAUTION!

Use an adjustable wrench to prevent the fitting 

adapters from overtightening while installing mating 

pipe connectors. Sensor damage will occur if the ports 

are overtightened.

Summary of Contents for FP-5070 Series

Page 1: ...e mail info omega com For latest product manuals www omegamanual info FP 5070 SERIES Flow Sensors Shop online at omega comSM User sGuide...

Page 2: ...pecifications without notice Servicing North America U S A Omega Engineering Inc Headquarters Toll Free 1 800 826 6342 USA Canada only Customer Service 1 800 622 2378 USA Canada only Engineering Servi...

Page 3: ...ft cable Pipe fitting adapter G 1 4 x 1 4 in NPT 2 included G 1 4 in port threads Upper body with electronic switch Lower body with built in rotor psi bar 6 9 100 5 5 80 4 1 60 2 8 40 1 4 20 0 40 40...

Page 4: ...ews required customer supplied 32 5 mm 1 28 in bolt circle 4 Wiring Details 4 1 Cable Extensions The standard 25 foot sensor cable can be extended to 300 m 1000 ft using 2 conductor shielded twisted p...

Page 5: ...supply Red Black Shield Freq IN Sen Pwr Freq IN Iso Gnd Open Collector Sensor Std Sensor FP 5072 FP 5072 FLOW FLOW Input Gnd 10k 5 to 24 VDC Black Shield Red Pull up resistor required 10 k recommended...

Page 6: ...pen or pencil body to adjust flow insert depth 7 Install rotor quad ring and upper body Hand tighten only Do not overtighten upper body or the lower body assembly tabs will break 8 Reprogram instrume...

Page 7: ...y OMEGA if the unit is found to be defective it will be repaired or replaced at no charge OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser including but not limite...

Page 8: ...city Indicators M U Turbine Paddlewheel Systems M U Totalizers Batch Controllers pH CONDUCTIVITY M U pH Electrodes Testers Accessories M U Benchtop Laboratory Meters M U Controllers Calibrators Simula...

Reviews: