Installation of FMG70B 

  

- 10 - 

 

M-5575/0416 

 
 

 

Installation can occur in horizontal and vertical pipes. The flow sensor is only suitable for 
application in completely filled pipe systems. 

 

As a matter of principle magnetic inductive flow sensors are widely independent from the 
flow profile. An inlet section is not absolutely necessary. 
To reach a most highly accuracy of the measurement, you should use straight inlet and 
outlet sections according to the inner diameter. The inlet section has to be at least 
10 x inner diameter; the outlet section 5 x inner diameter in order to achieve the specified 
accuracy. 

 

The inlet and outlet sections and gaskets must have the same or a slightly larger inside 
diameter than the measuring tube in order to achieve the specified accuracy. 

 

4.2  Mounting 

The FMG70B is installed directly into the pipeline. The compact design and light weight of the 
unit make wall-mounting unnecessary. 

 

IMPORTANT NOTICES: 

  Observe the flow direction indicated on the FMG70B.  

  Observe the mounting dimensions (

 § 9.5 "Dimensions"). 

 

  Select an appropriate location for installation (

 § 4.1 

"Installation instructions").  
To ensure the best possible measuring accuracy, a vertical 
installation position with increasing flow is preferable (no 
collecting of dirt deposits). 

  Wrap the FMG70B connections with 1 to 2 wraps of thread 

tape (e.g. Teflon

®

 tape).  

Wrap tape in a clockwise direction, viewed form the end, 
leaving the first two threads uncovered. 

  Make sure the tape does not intrude into the flow path.  

  Attach the FMG70B with arrow pointed in the direction of flow.  

  The fittings should be screwed into FMG70B hand tight.  

 
 

 

CAUTION! Material damage!  
Do not use excessive force. The FMG70B can be 
damaged. 

While tightening, counter the union nut on the hexagon of the 
process connection! 

If you do not counter it, the FMG70B can be damaged! 

 
 

Maximum Torque 

FMG71B - ½'' 

FMG72B - ½'' 

• ¾"

 

FMG73B - 1'' 

15 Nm 

15 Nm 

30 Nm 

 

  Use two wrenches to tighten the FMG70B an additional ¾ to 1 turn.  

When tightening, use a wrench (AF 1.063 or AF 1.338) to counter the process connection 
on the hexagon (flange) in place. 

 

 

 

 

 

 

Summary of Contents for FMG70B Series

Page 1: ...FMG70B Series Magnetic Inductive Flow Sensor...

Page 2: ...2 M 5575 0416...

Page 3: ...g 13 6 2 Switching on and off 13 6 3 Measuring mode 13 7 Maintenance and cleaning 15 7 1 Return shipment to the manufacturer 15 8 Disassembly and disposal 16 9 Technical data 17 9 1 Characteristics FM...

Page 4: ...is sign indicates dangers that cause personal injuries that can lead to health defects or cause considerable damage to property CAUTION Electric current This sign indicates dangers which could arise f...

Page 5: ...G70B It contains the most important data the connection diagram and the arrow for the flow direction Example Fig 1 1 Delivery unpacking and accessories All units have been carefully checked for their...

Page 6: ...d is only guaranteed by intended use The specified limits 9 Technical data may under no circumstances be exceeded Before installing the device check that the wetted materials of the device are compati...

Page 7: ...FMG70B must hold a relevant qualification This can be based on training or relevant tuition The personnel must be aware of this operating manual and have access to it at all times The electrical conne...

Page 8: ...ed in the middle of the measuring tube between the earthing sleeves The FMG70B does not need any moving parts to make measurements The inside of the measuring tube is completely open allowing the flui...

Page 9: ...pment is depressurized and has cooled down SUITABLE TOOLS Use only suitable tools of the correct size 4 1 Installation instructions CAUTION Risk of malfunction due to external magnetic fields Magnetic...

Page 10: ...OTICES Observe the flow direction indicated on the FMG70B Observe the mounting dimensions 9 5 Dimensions Select an appropriate location for installation 4 1 Installation instructions To ensure the bes...

Page 11: ...ed power Optional wirings Depending on the version an analog output can be optionally connected Connecting cable Suitable connection cables with molded coupling socket are available in various lengths...

Page 12: ...o not connect Connect the connecting cable according to your version and the pinout on the type plate Supply voltage FMG70B with frequency output Push Pull 1 NPN Open Collector PNP Open Collector 1 Pu...

Page 13: ...the connected supply voltage Switch on the supply voltage The green LED lights up once for 1 s The FMG70B is ready and goes into measuring operation 6 3 Measuring mode In measuring mode the green LED...

Page 14: ...ng and measuring mode 14 M 5575 0416 FMG70B with analog output According to the configuration of the FMG70B the analog output provides a voltage or current signal This signal is proportional to the me...

Page 15: ...e unit before return to Omega Costs incurred due to inadequate cleaning of the device and possible costs for disposal and or personal injuries will be billed to the operating company WARNING Risk of i...

Page 16: ...Prior to disassembly ensure that the equipment is switched off and is in a safe and de energized state the equipment is depressurized and has cooled down Disassembly Remove the electrical connectors...

Page 17: ...se rate pulses gal optional 2 2 000 4 7 500 1 000 4 3 700 250 4 750 Resolution gal pulse optional 2 0 0005 0 26 0 0001 0 001 0 26 0 0003 0 005 0 26 0 0013 Signal shape Square wave signal duty cycle 50...

Page 18: ...pressure 232 psi Process connection NPT male thread NPT male thread NPT male thread 1 NPT male thread The maximum ambient temperature depends on the temperature of the medium and the wiring of the FM...

Page 19: ...Technical data Technical changes reserved 19 9 4 Temperature limits The maximum ambient temperature depends on the medium temperature and the version of the FMG70B...

Page 20: ...Technical data 20 M 5575 0416 9 5 Dimensions FMG71B and FMG72B NPT only for FMG72B The cross section of the FMG72B does not taper to 0 16 in FMG73B...

Page 21: ...For your notes Technical changes reserved 21 For your notes...

Page 22: ...For your notes 22 M 5575 0416 For your notes...

Page 23: ...Technical changes reserved 23...

Page 24: ...24 M 5575 0416 M 5575 0416...

Reviews: