background image

11

• 

Conductivity is less than 20 µS/cm.

• Electronic 

component 

failure.

• 

4-20 mA is not scaled same as Loop 
device.

• 

Loop device is not scaled same as 
Magmeter.

• 

Range Jumper not placed correctly.

• Defective 

Magmeter

• 

Magmeter installed too close to 
upstream obstruction.

• 

Magmeter electrodes are coated with 
solids.  

• 

Magmeter electrodes exposed to air 
bubbles/pockets.

• 

Electrical noise is interfering with the 
measurement.

• 

New sensor, metal surface not 
properly conditioned.

• 

Output is not 0 when fl ow is stopped.

• Frequency 

or 

Current

 

output is erratic.

• Output 

is 

22.1 

mA.

• 

Electrode not adequately conditioned.

• 

Pipe is empty, Magmeter is not in fl uid.

• 

Electrical noise is interfering with the 
measurement.

• Defective 

Magmeter

Symptom

Possible Cause

Possible Solution

• 

Frequency output is inoperative

• 

Loop output is inperative.

• 

Move the Magmeter upstream at least 
10 pipe diameters from obstruction.

• 

Clean the electrodes with soft cloth. 
Do not use abrasives.

• 

Eliminate air bubbles in the pipe.

• 

Remove the Magmeter and reinstall 
with the fl ow direction arrow on the 
sensor body pointed DOWNSTREAM.

• 

Modify grounding as required 
to protect the Magmeter from 
interference.

• 

Soak sensor overnight in fl uid.

10.2 Troubleshooting

• 

Soak sensor overnight in fl uid.

• 

Confi gure pipe so electrodes are 
always in fl uid.

• 

Modify grounding as required 
to protect the Magmeter from 
interference.

• 

Set low fl ow cutoff higher.

• 

Return to factory for service.

• 

Respan Loop device to match 
Magmeter.

• Set 

Range 

Jumper 

correctly.

• 

Return to factory for service.

• 

FMG-3000 is wrong model.

• 

Blue jumper not in correct position.

• 

Wiring is not correct.

• 

Frequency input to other 
manufacturer's fl ow instrument does 
not have pull-up resistor.

• 

Frequency model is FMG-3001 and 
FMG-3101 series.

• Place 

blue 

jumper 

correctly. 

(Sec. 

pg. 9)

• 

Check wiring, make corrections.

• Install 

10k

 resistor. Sec 8.1, pg. 6)

• 

Unsuitable application for Magmeter.

• 

Return to factory for service.

• 

4-20 mA output is incorrect.

10. Maintenance

The FMG-3000 series Magmeter requires very little maintenance.  There are no user-serviceable components in the Magmeter.
• 

If the fl uid contains deposits and solids that may coat the electrodes, a regular cleaning schedule is recommended.

• 

Do not use abrasive materials on the metal electrodes.  Clean with soft cloth and mild detergent only.

• 

Use a cotton swab and mild detergent to remove deposits on the metal electrodes at the tip of the sensor.

10.1. Environmental 

Recommendations:

• 

When used properly, this product presents no inherent danger to the environment.

• 

Please follow local ordinance when disposing of this or any product with electronic components.

Troubleshooting with the RED and BLUE lights

The FMG-3000 uses two colored LEDs to indicate the status of the instrument. 
They are located at the top of the magmeter, inside the clear plastic cap.

No Lights: 

 

The power is off or the sensor is not connected

Solid Blue (D7):   

The power is on but there is no fl ow in the pipe.

Blinking Blue (D7): 

Normal operation, blink rate is proportional to the fl ow rate.

Alternating Red-Blue: 

Empty pipe indication (electrodes are not wet.)

Blinking Red (D6): 

System errors (Electrical noise interference)

Solid Red (D6):   

Instrument error (defective electronics component) 

1

2

3

4

JP2

D7

D6

Flow

Flow

Summary of Contents for FMG3000 SERIES

Page 1: ...eter User sGuide omega com omega comTM www omega com e mail http omegamanual info For latest information and product manual visit www omegamanual info ISO9001 CERTIFIED CORPORATE QUALITY STAMFORD CT I...

Page 2: ...2378 1 800 622 BEST Engineering Service 1 800 872 9436 1 800 USA WHEN TELEX 996404 EASYLINK 62968934 CABLE OMEGA Mexico En Espa ol 001 203 359 7803 e mail espanol omega com FAX 001 203 359 7807 info o...

Page 3: ...e Magmeter into the pipe Use Omega installation ttings ONLY The installation tting is critical to Magmeter performance Sec 3 4 Pg 3 3 Connect POWER and OUTPUT wiring FMG 3001 and FMG 3101 Frequency ou...

Page 4: ...Current output 4 to 20 mA Programmable and reversible Loop Accuracy 32 A max error 25 C 24 VDC Temp drift 1 A per C max Power supply rejection 1 A per V Isolation Low voltage 48 VAC DC from electrode...

Page 5: ...straight pipe immediately upstream of the sensor Locating the sensor in a trap or where the ow is upward helps to protect the sensor from exposure to air bubbles when the system is in operation NOTE T...

Page 6: ...to the smaller terminal block These connections should always remain connected to prevent inadvertent damage or miswiring The terminals on the FMG 3000 Magmeter are designed for conductors from 16 AWG...

Page 7: ...3000 Use anged grounding rings or metal electrodes on plastic pipes or metal clamps on metal pipes Fluid grounds must be in direct contact with the uid and as near to the Magmeter as possible The shie...

Page 8: ...TTING K Factor K Factor 20 mA 20 mA IN TYPE Gallons Liters in GPM in LPM SCH 80 IRON SADDLE ON SCH 80 PIPE 2 FP 5320GI 194 85 51 48 153 96 582 75 2 FP 5325GI 142 28 37 59 210 86 798 10 3 FP 5330GI 87...

Page 9: ...5307C 1381 48 364 99 21 72 82 19 1 FP 5310C 857 98 226 68 34 97 132 34 1 FP 5312C 445 17 117 61 67 39 255 07 1 FP 5315C 325 56 86 01 92 15 348 78 SCH 80 PVC SADDLES FOR SCH 80 PVC PIPE 2 FP 5320S 193...

Page 10: ...08 412 86 2 FP 5120PO 156 87 41 45 191 24 723 83 PVDF FITTINGS DIN ISO BS ANSI FP 5105 1946 49 514 26 15 41 58 34 FP 5107 1158 05 305 96 25 91 98 05 1 FP 5110 749 09 197 91 40 05 151 58 1 FP 5112 439...

Page 11: ...0 36 84 9 73 814 34 3082 28 4 FMG 5350 29 28 7 73 1024 70 3878 50 4 FMG 5360 20 29 5 36 1478 26 5595 21 8 FMG 5380 11 73 3 10 2557 72 9680 96 10 FMG 5381 7 45 1 97 4028 83 15249 1 12 FMG 5382 5 24 1 3...

Page 12: ...PPER TEES FITTING ON COPPER PIPE SCH L FP 5305CU 2406 30 635 75 12 47 47 19 FP 5307CU 1174 77 310 37 25 54 96 66 1 FP 5310CU 672 28 177 62 44 62 168 90 1 FP 5312CU 402 84 106 43 74 47 281 87 1 FP 5315...

Page 13: ...3000 is wrong model Blue jumper not in correct position Wiring is not correct Frequency input to other manufacturer s ow instrument does not have pull up resistor Frequency model is FMG 3001 and FMG...

Page 14: ...PVDF TI OMEGAMAG Blind Freq PVDF Ti 5 8 OMEGAMAG with 4 20 mA Loop Output FMG3002 PP OMEGAMAG Blind Loop PP 316SS 4 FMG3102 PP OMEGAMAG Blind Loop PP 316SS 5 8 FMG3202 PP OMEGAMAG Blind Loop PP 316SS...

Page 15: ...t exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS Equipment sold by OMEGA is not i...

Page 16: ...rs Air Velocity Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pump...

Reviews: