REPLACING ORIFICE:
This can be accomplished without removing the unit from its mounting or plumbing.

1. 

Turn off supply pressure and unscrew the brass orifice assembly located on the side of the housing with the gauge
port.

NOTE: Small sealing o-ring may remain inside of the housing. If it does, remove it with a paper clip or some other small
probe. The replacement assembly will contain this o-ring.

2. 

Install the new orifice assembly making sure the o-ring is seated on the end of the screw.

CLEANING INTERNAL SUPPLY VALVE:
1. 

Turn off the supply pressure.

2. 

Use a 9/16" socket or wrench to unscrew the brass plug in the bottom of the transducer.

NOTE: Take care not to lose the supply valve spring which is retained by the bottom plug. 

3. 

Clean out any dirt or debris and reassemble, making sure the stem of the supply valve is nested in the supply valve
spring.

AGENCY APPROVALS, SPECIAL NOTES, AND CAUTIONS

INTRINSIC SAFETY

All 510 and 511 Series transducers are rated intrinsically safe by both FM and CSA for:

CLASS I, DIVISION 1, GROUPS A,B,C,D HAZARDOUS LOCATIONS.

Proper FM-approved intrinsically-safe wiring requires external FACTORY MUTUAL RESEARCH CORPORATION ENTITY-
APPROVED SINGLE-CHANNEL barriers to be selected, based upon MAXIMUM ENTITY PARAMETERS of 510 and 511 Series
transducers: 

ENTITY PARAMETERS:

Vmax = 28 V, Imax = 150 mA, Ci = 0.22uF, Li = 0 mH. 
Voc and Isc of a barrier shall not exceed Vmax and Imax of the transducer.
(Li + Lwiring) and (Ci + Cwiring) shall not exceed La and Ca of a barrier.

NOTICE: For proper FM and CSA approved intrinsically-safe wiring, request Drawing Number 990-439-000 from the
Factory.

NONINCENDIVE

All 510 and 511 Series transducers are approved as NONINCENDIVE by FM and approved as suitable by CSA for:

CLASS I, DIVISION 2, GROUP A, B, C, D HAZARDOUS LOCATIONS.

A barrier is not necessary when these transducers are in these locations.

ENCLOSURES

Compliance with 

NEMA 4X

and 

CSA ENC4

enclosure ratings require that the screw-on cover has the O-ring installed. In case

of a need for replacement parts, see TABLE 3.

M-4109/1104 IP510, EP510, IP511, EP511 SERIES

A

7

)-T1001.qxd  4/11/05  3:23 PM  Page 7

Summary of Contents for EP510 Series

Page 1: ...omega com e mail info omega com For latest product manuals omegamanual info EP510 IP510 EP511 IP511 SERIES Electroneumatic Converters Shop online at User sGuide MADE IN ...

Page 2: ...ce Managed by the United Kingdom Office Toll Free 0800 466 342 TEL 33 0 161 37 29 00 FAX 33 0 130 57 54 27 e mail sales omega fr Germany Austria Daimlerstrasse 26 D 75392 Deckenpfronn Germany Toll Free 0800 6397678 TEL 49 0 7056 9398 0 FAX 49 0 7056 9398 29 e mail info omega de United Kingdom OMEGA Engineering Ltd ISO 9001 Certified One Omega Drive River Bend Technology Centre Northbank Irlam Manc...

Page 3: ...G In order to get optimal service from this transducer and ensure warranty coverage the following MUST be followed The supply air quality to this instrument must be instrument quality air as defined by ISA Standard 57 0 01 1996 1 Dew point not higher than 35 F 2 No particulates larger than 3 microns in size 3 Maximum oil content of 1 ppm No mechanical adjustments or calibrations are necessary or a...

Page 4: ... 32 screws using threaded holes in the bottom of a transducer NEMA 4X transducers may be mounted to a panel with three No 10 32 screws using threaded holes in the back of a transducer or with four No 8 32 screws using threaded holes in the bottom of a transducer In the case of back mount ing if the panel extends towards the screw on cover a 3 16 inch thick spacer MUST be used between the back of t...

Page 5: ...ould installation next to high electromagnetic interference be necessary WARNING In explosive atmospheres electrical power must be removed from the transducer before attempting to remove the cover and until the cover is fully reinstalled Failure to do so may result in electrical spark or explosion CAUTION Care must be used when inserting wires into the NPT port Wires must not enter below the circu...

Page 6: ...nsducers should provide more than one million cycles without failure If a situation should occur in which the transducer s behavior is abnormal the cause is usually related to a pneumatic problem ELECTRICAL MAINTENANCE An electrical problem must be isolated by a skilled technician The power source and all wiring should be checked first Circuit board failures are very rare and can be confirmed by t...

Page 7: ...ries transducers are rated intrinsically safe by both FM and CSA for CLASS I DIVISION 1 GROUPS A B C D HAZARDOUS LOCATIONS Proper FM approved intrinsically safe wiring requires external FACTORY MUTUAL RESEARCH CORPORATION ENTITY APPROVED SINGLE CHANNEL barriers to be selected based upon MAXIMUM ENTITY PARAMETERS of 510 and 511 Series transducers ENTITY PARAMETERS Vmax 28 V Imax 150 mA Ci 0 22uF Li...

Page 8: ...plied In case of a need for replacement parts follow TABLE 4 EXPLOSION PROOF FOR CLASS I DIV 1 GROUP B C D DUST IGNITION PROOF FOR CLASS II DIV 1 GROUP E F G SUITABLE FOR CLASS III LOCATIONS M 4109 1104 IP510 EP510 IP511 EP511 SERIES A 8 TABLE 3 NEMA 4X REPLACEMENT COVER O RINGS PART NAME PART NUMBER O RING SEAL VITON 214 649 000 242 O RING SEAL BUNA N 214 649 000 240 TABLE 4 NEMA 4X REPLACEMENT P...

Page 9: ...ngs 010137 002 8 Standard outlet range orifice with Buna N O rings 010137 001 9 Standard outlet range orifice with Viton O rings 010137 003 10 Hirschmann Connector Kit 3 prong plug O ring sealed 010142 000 11 Pressure Gauge Kit 15 PSI 010138 000 12 Pressure Gauge Kit 30 PSI 010138 001 13 Pressure Gauge Kit 60 PSI 010138 002 14 Pressure Gauge Kit 160 PSI 010138 003 EP511 AND IP511 SIDE VIEW SIDE VI...

Page 10: ... F to 160 F Storage Temperature Range Buna N elastomers Viton elastomers 40 F to 200 F 15 F to 200 F Vibration Effect Less than 0 5 of SPAN per 1G 5 2000 Hz 3G maximum 3 axes Mounting Position Effect Not measurable Loop Load I P transducer Less than 10 VDC drop at 20 mA Less than 12 VDC drop at 50 mA Supply Voltage E P Transducer Intrinsically Safe Nonincendive General Purpose 9 VDC to 28 VDC less...

Page 11: ...otherwise shall not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS Equipment sold by OMEGA is not intended to be used nor shall it be used 1 as a Basic Component under 10 CFR 21 NRC used in or with any nuclear installation or activity or 2 in medical applications or used on humans...

Page 12: ...tors 䡺 Turbine Paddlewheel Systems 䡺 Totalizers Batch Controllers pH CONDUCTIVITY 䡺 pH Electrodes Testers Accessories 䡺 Benchtop Laboratory Meters 䡺 Controllers Calibrators Simulators Pumps 䡺 Industrial pH Conductivity Equipment DATA ACQUISITION 䡺 Data Acquisition Engineering Software 䡺 Communications Based Acquisition Systems 䡺 Plug in Cards for Apple IBM Compatibles 䡺 Data Logging Systems 䡺 Reco...

Reviews: