Trouble shooting 

 

Problem 

Possible cause 

Solution 

No LED signal 

 

Faulty or no power supply 

 

PCB defective 

 

Check power supply 

 

Replace PCB 

Pressing TEST 

button has no 

effect 

 

Blocked valve 

 

System pressure above 16bar / 

232psi 

 

Clean the valve 

 

Check system pressure 

Condensate 

discharge only 

when TEST button 

is being pressed 

 

Faulty installation 

 

Condensate inlet line with 

insufficient slope 

 

Sensor extremely dirty 

 

Check if device is installed in 

accordance with installation 

recommendations 

 

Install venting line 

 

Clean sensor housing 

Air keeps blowing 

out 

 

Blocked valve 

 

Wear 

 

Clean the valve 

 

Replace worn parts 

 

Check if intense corrosion is 

present in the system 

Permanent red LED 

flashes 

 

Device is in one of production 

modes 

 

Contact supplier 

 

Warranty exclusion 

 

The guarantee shall be void if: 

 

The installation and operating manual was not followed with respect to installation, 

initial commissioning and maintenance. 

 

The unit was not operated properly and appropriately. 

 

The unit was operated when it was clearly defective. 

 

Non-original spare parts or replacement parts were used. 

 

The unit was not operated within the permissible technical parameters. 

 

Unauthorized constructional changes were made to the unit or if the unit has been 

opened/disassembled by an unauthorized person. 

 

 

 

 

OMEGA AIR d.o.o. Ljubljana 

Cesta Dolomitskega odreda 10 

SI-1000 Ljubljana, Slovenia 

Tel.: +386 (0)1 200 68 00 

Fax.: +386 (0)1 200 68 50 

E-mail: 

[email protected]

 

www.omega-air.si 

 

Summary of Contents for ECD 15B

Page 1: ...re installing electronic drain unit into service Trouble free and safe operating of the unit can only be guaranteed if recommendations and conditions stated in this manual are respected Installation a...

Page 2: ...235 scfm 90 l h 0 0529 scfm 150 l h 0 0882 scfm Operating temperature range 1 5 65 C 1 5 65 C 1 5 65 C 1 5 65 C Inlet connection G 1 2 G 1 2 G 1 2 G 1 2 Outlet connection G 1 8 G 1 8 G 1 8 G 1 8 Power...

Page 3: ...ualified electrician Do not exceed max operating pressure or operating temperature range see data label Do not use the device in hazardous areas with potentially explosive atmospheres Use original spa...

Page 4: ...al to electronic board Electromagnetic valve 4 is than opened to discharge accumulated condensate through outlet connection 5 When reservoir 2 has been emptied the valve 4 closes back without any loss...

Page 5: ...mmended Install ball valves 2 only Recommended connection 4 to water oil separator 1 2 The inclination of the unit must not exceed 5 in both axes If device is not installed correctly it could cause fa...

Page 6: ...d air prevents the condensate being purged from drain 5 During installation ensure that no water pockets are formed in the piping 6 7 8 When drainage is to take place directly from a pipeline it is re...

Page 7: ...connections cannot be used as condensate inlet at the same time 13 14 STANDARD INSTALLATION Upper connection Inlet Back connection Closed VENTING LINE INSTALLATION Upper connection Air ventilation Ba...

Page 8: ...Three flashes ECD 90B 4 Four flashes ECD 150B Operating LED indicates a condensate sensor output 1 Green FLASHES Sensor detects no water 2 Green ON Condensate is detected 3 Red ON Alarm mode Short fla...

Page 9: ...ate is doubled This mode lasts for five minutes In case the reservoir empties during overload mode the drain enters normal mode again Otherwise it goes into alarm mode ALARM If drain was still not abl...

Page 10: ...nge sealings Attention Before beginning maintenance work take the drain out of operation cut off the power supply and depressurize the unit Service kits Service Kit type Order number Description Servi...

Page 11: ...pring 12 Plunger 13 Valve housing 14 O ring 5 8x1 5 15 Coil 16 O ring 5 8x1 5 17 Valve connector 18 Screw M3 DIN912 19 Screw M3x30 20 Extension hose 21 Internal strainer 22 Sealing 23 O ring 7x2 24 Bo...

Page 12: ...ce worn parts Check if intense corrosion is present in the system Permanent red LED flashes Device is in one of production modes Contact supplier Warranty exclusion The guarantee shall be void if The...