ECD 15B / 40B / 90B / 150B - Installation and operating manual 

 

 

Operating modes 

 

NORMAL 

When sensor detects condensate the valve opens up to one second to discharge. The exact 

period depends on type of a drain. Minimal time between two discharges is 5 seconds.  

OVERLOAD 

If sensor detects condensed water continuously for 90 seconds, drain enters overload mode. 

In this mode, the valve is opened longer and the time between discharges is shorter. 

Therefore, the amount of discharged condensate is doubled. This mode lasts for five 

minutes. In case the reservoir empties during overload mode, the drain enters normal mode 

again. Otherwise, it goes into alarm mode. 

ALARM 

If drain was still not able to discharge all condensate it enters alarm mode. In this mode, the 

valve is opened for five seconds every half minute. In case the reservoir empties during 

alarm mode, drain enters normal mode again.  

Alarm output 

 

The ECD comprises an alarm output that is voltage free. The output is connected to the red 

signal logically. The output is in high impedance state when the red LED is on or when ECD 

electric supply is off. 

 

 

Alarm 

Red 

LED 

Alarm XA 

U

OUT

 

I

OUT

 

(I

out

 max 20mA) 

(U

out

 max 24V) 

Summary of Contents for ECD 15B

Page 1: ...re installing electronic drain unit into service Trouble free and safe operating of the unit can only be guaranteed if recommendations and conditions stated in this manual are respected Installation a...

Page 2: ...235 scfm 90 l h 0 0529 scfm 150 l h 0 0882 scfm Operating temperature range 1 5 65 C 1 5 65 C 1 5 65 C 1 5 65 C Inlet connection G 1 2 G 1 2 G 1 2 G 1 2 Outlet connection G 1 8 G 1 8 G 1 8 G 1 8 Power...

Page 3: ...ualified electrician Do not exceed max operating pressure or operating temperature range see data label Do not use the device in hazardous areas with potentially explosive atmospheres Use original spa...

Page 4: ...al to electronic board Electromagnetic valve 4 is than opened to discharge accumulated condensate through outlet connection 5 When reservoir 2 has been emptied the valve 4 closes back without any loss...

Page 5: ...mmended Install ball valves 2 only Recommended connection 4 to water oil separator 1 2 The inclination of the unit must not exceed 5 in both axes If device is not installed correctly it could cause fa...

Page 6: ...d air prevents the condensate being purged from drain 5 During installation ensure that no water pockets are formed in the piping 6 7 8 When drainage is to take place directly from a pipeline it is re...

Page 7: ...connections cannot be used as condensate inlet at the same time 13 14 STANDARD INSTALLATION Upper connection Inlet Back connection Closed VENTING LINE INSTALLATION Upper connection Air ventilation Ba...

Page 8: ...Three flashes ECD 90B 4 Four flashes ECD 150B Operating LED indicates a condensate sensor output 1 Green FLASHES Sensor detects no water 2 Green ON Condensate is detected 3 Red ON Alarm mode Short fla...

Page 9: ...ate is doubled This mode lasts for five minutes In case the reservoir empties during overload mode the drain enters normal mode again Otherwise it goes into alarm mode ALARM If drain was still not abl...

Page 10: ...nge sealings Attention Before beginning maintenance work take the drain out of operation cut off the power supply and depressurize the unit Service kits Service Kit type Order number Description Servi...

Page 11: ...pring 12 Plunger 13 Valve housing 14 O ring 5 8x1 5 15 Coil 16 O ring 5 8x1 5 17 Valve connector 18 Screw M3 DIN912 19 Screw M3x30 20 Extension hose 21 Internal strainer 22 Sealing 23 O ring 7x2 24 Bo...

Page 12: ...ce worn parts Check if intense corrosion is present in the system Permanent red LED flashes Device is in one of production modes Contact supplier Warranty exclusion The guarantee shall be void if The...