Setup & Configuration
3
3-12
You must set the wire jumpers located on the back of your
meter to match the analog output type you selected here in
the setup process.
Figure 3-18. Analog Output Options
Scaling
Here you can scale the analog output to correspond to the process reading value.
4-20 mA Example:
This table shows analog output values you should expect if you set 4mA = 0 psig
and 20mA = 1000 psig.
Process Reading
Analog Output Value
0 psi
4.00 mA
250 psi
8.00 mA
500 psi
12.00 mA
750 psi
16.00 mA
1000 psi
20.00 mA
NOTE: