background image

Alarm Type Selection

The lower display will either indicate 

DBAND

 or 

ADJ_H

.

If 

DBAND

 is selected, each relay will operate with 1% of full-

scale deadband between set and reset. 
If 

ADJ_H

 is selected, each output relay will have an adjust-

able set point and an adjustable reset point. 
Use the 

s

 or the 

t

 buttons to select either 

DBAND 

or 

ADJ_H

When to desired mode is displayed, press and release the 

SEL

 

button to move on to the next parameter.

LED Alarm Annunciator Function Selection

This setting lerts the operator to an alarm conditionby blinking 
the LEDs. The choices are
Automatically acknowledge: 

A_ACK

Manually acknowledge: 

M_ACK

No acknowledgement: 

NO_AN

Use the 

s

 or 

t

 buttons to cycle through the three choices.

A_ACK

: An alarm condition will be automatically acknowl-

edged when the alarm condition clears. When an alarm condi-
tion occurs, the LED for that alarm will begin to blink red until 
it has been manually acknowledged by a pressing the 

TEST 

button, or until the alarm condition no longer exists. If an alarm 
is manually acknowledged, the LED will be steadily red while 
the alarm condition continues to exist. The LED will be steadily 
green whenever no alarm condition exists.

M_ACK

: An alarm condition must be manually acknowledged. 

When an alarm condition occurs, the LED for that alarm will 
blink red if the alarm condition exists or blink green if the alarm 
condition no longer exists. The LED will continue to blink until 
it has been manually acknowledged by a pressing the 

TEST 

button. Once an alarm has been acknowledged, the LED will be 
steadily red while the alarm condition exists or green when the 
alarm no longer exists.

NO_AN

: The LEDs will not blink. When an alarm condition 

occurs, the LED associated with that alarm will be steadily red 
if the alarm condition exists, or green if the alarm condition 
no longer exists. In addition, the LCD display for ALARM1 and 
ALARM2 will not be displayed during alarm conditions.
When the lower display indicates the desired annunciator 
action, press and release the 

SEL

 button to move on to the 

next parameter.

Fixed Deadband 

DBAND

 Alarm Setup

Alarm 1 Type in 

DBAND 

Mode

If 

ADJ_H 

was selected, skip to the Relay Power Up State 

Section.
Use the 

s

 or 

t

 buttons to select either

SP1_L

 or 

SP1_H

If 

SP1_L

 is selected, Alarm 1 will be a LOW alarm. 

Alarm 1 will be SET when the pressure falls below Setpoint 1.
Alarm 1 will be RESET when the pressure rises above Setpoint 
1 plus the deadband. The fixed 1% deadband is .01 x the full 
scale range of the gauge.
If 

SP1_H

 is selected Alarm 1 will be a high alarm. 

Alarm 1 will be SET when the pressure rises above Setpoint 1.
Alarm 1 will be RESET when the pressure falls below Setpoint 
1 minus the deadband. The fixed 1% deadband is .01 x the full 
scale range of the gauge.
When the desired alarm type is displayed, press and release the 

SEL

 button to move to Alarm 2.

Alarm 2 Type in 

DBAND 

Mode

Use the 

s

 or 

t

 buttons to select either

SP2_L

 or 

SP2_H

If 

SP2_L

 is selected, Alarm 2 will be a LOW alarm. 

Alarm 2 will be SET when the pressure falls below Setpoint 1.
Alarm 2 will be RESET when the pressure rises above Setpoint 
2 plus the deadband. The fixed 1% deadband is .01 x the full 
scale range of the gauge.
If 

SP2_H

 is selected Alarm 2 will be a high alarm. 

Alarm 2 will be SET when the pressure rises above Setpoint 1.
Alarm 2 will be RESET when the pressure falls below Setpoint 
2 minus the deadband. The fixed 1% deadband is .01 x the full 
scale range of the gauge.
When the desired alarm type is displayed, press and release the 

SEL

 button to move to the next parameter.

Gauge Configuration 

From the normal operating mode, press and hold the 

TEST

 and 

s

 buttons. 

Then press the 

SEL

 button. 

Release all buttons when the display indicates 

CFG

.

Before the gauge enters the Configuration mode, the display 
initially indicates  _ _ _ _  with the first underscore blinking, 
and 

CFGPC

 on the lower display. 

Enter the pass code as described below. 

Pass Code Entry 

A pass code is required to configure the gauge. Additional levels 
of security may be enabled by defining separate pass codes 
for calibration, configuration, output test, and set point adjust 
modes. See Changing the User-Defined Pass Code at the end of 
this manual to change pass codes.
Functions in user configuration mode 
  Restore original factory configuration 
  Enable/disable zero tare function 
  Choosing 1% deadband or adjustable hysteresis alarm mode 
  Operation for blinking alarm LEDs 
  Set point modes (high alarm/low alarm or state at power-up) 
  Relay action mode (normal/reverse) 
  Enable/disable pass code for output test and set point adjust
When the gauge requests a pass code, the display indicates  

____

  with the first underscore blinking, and either 

TSTPC

CFGPC

CALPC

 on the lower display. All three pass codes 

are initially set to the factory default of 

3510

.

Note: During pass code entry the LEDs will be off and the gauge 
will not respond to changes in pressure. The relays will maintain 
their prior state. The gauge will automatically revert to the nor-
mal operation if no buttons are ressed for approx.y 15 seconds.
Use the 

s

 and 

t

 buttons to set the left-most digit to 3.

Press and release the 

SEL

 button to index to the next position. 

The 3 will remain, and the second position will be blinking.
Use the 

s

 and 

t

 buttons to select 5.

Press and release the 

SEL

 button to index to the next position. 3 

5 will remain, and the third position will be blinking.
Use the 

s

 and 

t

 buttons to select 1.

Press and release the 

SEL

 button to index to the next position. 3 

5 1 will remain, and the fourth position will be blinking.
Use the 

s

 and 

t

 buttons to select 0.

Press and release the 

SEL

 button to proceed.

If an incorrect pass code was entered, the gauge will to exit to 
the normal operating mode. Upon successful pass code entry, 
follow the steps in the appropriate section of this manual.
Note: To exit a mode at any time, press and hold the 

SEL

 button 

until the display indicates  – – – – .

Restore Factory Configuration

The upper display will be blank, and the lower display will 
display either 

USER_

 or 

FCTRY

.

Use the 

s

 or 

t

 buttons to select either 

USER_

 or 

FCTRY

.

If 

USER_

 is selected, the existing user configuration will be 

retained and can be modified in the following steps. 
If 

FCTRY

 is selected, the existing user configuration will be 

replaced with the factory configuration. It can be modified in 
the following steps. 
When the desired setting is displayed, press and release the 

SEL

 button to move on to the next parameter.

Zero Tare Configuration

The upper display will be blank, and the lower display will 
indicate either 

ZTARE

 or 

NOZTR

.

Use the 

s

 or 

t

 buttons to select either 

ZTARE

 or 

NOZTR

If 

ZTARE

 is selected, the user will be able to manually zero 

the gauge from the normal operating mode.
If 

NOZTR

 is selected the user will be prevented from zeroing 

the gauge from the normal operating mode. This is default set-
ting for absolute reference ranges. 
When the desired setting is displayed, press and release the 

SEL

 button to move on to the next parameter.

Types of Gauges 

Gauge reference models read zero with the gauge port open. 
Compound ranges read vacuum in inches of Mercury, pressure 

in psig, and zero with the gauge port open.
1000 psi and higher sensors are a sealed-reference type. They 

read zero with the gauge port open are internally referenced to 

14.7 psi. They function like gauge reference sensors.
Absolute reference gauges read zero at full vacuum and atmo-

spheric pressure with the gauge port open. Note that readings 

of atmospheric pressure vary continuously. 

Gauge Wiring Diagram

Gauge Power Connections 

The 2-conductor cable RED and BLACK leads is for the gauge 
power supply. Note the relay cable also has red and black wires. 
Do not connect power to them.
Connect to 8-24 VAC, 50/60Hz or 9-32 VDC. The gauge will 
operate on either AC or DC power, either polarity. An unregu-
lated power supply can be used. Note that 24 VAC transformers 
with small loads may operate at voltages over the 24 VAC limit. 
The supply voltage, when within the stated ranges, has negli-
gible effect on the gauge calibration. Operation below 9 VDC 
or 8 VAC may cause erratic or erroneous readings or output.
When operating multiple gauges from the same power supply, 
refer to the mA rating in the specifications to ensure adequate 
power. Route the wires away from heat sources and moving 
equipment.

Power Up 

The gauge is powered on whenever a supply voltage is applied. 
Warm-up time is negligible. The gauge may be left on at all times. 
All configuration information is stored in non-volatile memory. 
When power is first applied, the gauge proceeds through a 
startup sequence. During the startup sequence, relays are de-
energized and the status LEDs are off.
1. The firmware version number is displayed briefly
2. All active display segments are turned on for approx. 1 second.
3. The full scale pressure is indicated for approx. 1 second while 

the engineering units and FS (full scale) are indicated for 1/2 
second on the character display.

4. The display is tested again for approximately 1 second.
The gauge then proceeds to the normal operating mode. 

Alarm Contact Rating and Protection 

The alarm contacts are rated at 1A/24VDC or 0.5A/115VAC. 
Using mechanical relay contacts above their rating, or with large 
inductive loads, will shorten their life. For inductive loads, RC 
snubbers or arc suppression devices are required to protect the 
contacts. For large loads a higher capacity contactor is required. 
No internal fusing is included in the alarm contact circuits. The 
alarm outputs should be externally fused by the user in applica-
tions where good design practice dictates.

Alarm Types 

The factory default configuration is 1% fixed deadband mode, 
zero tare enabled, and no pass code required for test function.
Alarms may be configured to operate in fixed deadband mode 
or adjustable hysteresis mode. 
In the fixed deadband mode, the alarm set/reset point deadband 
is factory set to 1% of full-scale. Each alarm may be configured 
as either HI or LO with a user adjustable alarm set point for 
each relay.
In the adjustable hysteresis mode, two independent set and 
reset trip points are user adjustable for each relay. The set 
or reset state at power up when between trip points is user 
configurable.

DPG1000ADA Series Digital Pressure Gauges With Alarms

2

Alarm Contact Ratings

0.5A/115VAC, 

1A/24VDC,  

non-inductive

6-conductor relay wires

BLACK NC Normally Closed

SPDT 

1

RED

C Common
NO Normally Open

GREEN

NC Normally Closed

SPDT 

2

BROWN

C Common

BLUE

NO Normally Open

Power wires

BLACK

8-24 VAC 50/60 Hz or  

9-32 VDC

RED

NC 1 

C 1 

NO 1

NC 2 

C 2 

NO 2

DPG1000ADA

Reviews: