![background image](http://html1.mh-extra.com/html/omega/dp400tp/dp400tp_user-manual_737784008.webp)
8 -
DP400S - User manual
4
Dimensions and Installation
45 x 91 mm
Front panel cut-out
kg
96 mm
48
mm
Memory Card
48
mm
5
10
2
÷15
mm
Suggested thickness
USB
(optional)
DP-USB-CARD
5
Electrical wirings
Although this controller has been designed to resist noises in an industrial
environment, please notice the following safety guidelines:
• Separate control lines from the power wires.
• Avoid the proximity of remote control switches, electromagnetic meters,
powerful engines.
• Avoid the proximity of power groups, especially those with phase control.
For permanently connected equipment
:
• supply wiring must be ≥18 AWG with cables suitable for temperatures > 70° C;
• for requirements about any external switch or circuit-breaker see EN 61010-1
par. 6.11.3.1 and about external overcurrent protection devices see EN
61010-1 par. 9.6.2; the switch or circuit-breaker must be near the equipment.