Reference Section: Programming Mode (PRoG)
Navigate to the desired setting. Settings include the following:
ACtN
–
Determines the action direction for control
dEAd
–
Sets the deadband value; the deadband value is applied in the
same units as the process variable to one side of Setpoint as determined by
the
ActN
direction
S
.
PNt
–
Allows either Setpoint 1 or Setpoint 2 to be specified as the
target value; Setpoint 2 can be set to track Setpoint 1 using the deviation
(
dEVI
) option (
—
a useful feature when setting
up for heat/cool operation
Select the indicated setting.
For
ACtN
, select the correct setting. Settings include the following:
RVRS
–
Off when Process Value is > Setpoint, and on when Process Value
is < Setpoint (e.g., heating); deadband is applied below Setpoint (factory
default)
dRCt
–
Off when Process Value is < Setpoint, and on when Process Value
is > Setpoint (e.g., cooling); deadband is applied above Setpoint
For
dEAd
, set the desired value. (The default is 5.0.)
Select the indicated
ACtN
setting, or confirm the
dEAd
value.
7.4.1.5
Output as Alarm 1 (PRoG > oUt1
–
oUt6 > ModE >
ALM.1)
Select this Output to be an Alarm using the Alarm 1 (
ALM.1
) configuration.
7.4.1.6
Output as Alarm 2 (PRoG > oUt1
–
oUt6 > ModE >
ALM.2)
Select this Output to be an Alarm using the Alarm 2 (
ALM.2
) configuration.
7.4.1.7
Retransmission (PRoG > oUt1
–
oUt6 > ModE >
RtRN)
Select Retransmission (
RtRN
) as the Operating Mode for the output. This option is
only available for analog outputs. Scaling is performed using absolute values
—
not
calculated counts. The retransmission signal type (voltage or current and range) is
set for this output using the
7.4.3 Analog Output Range (PRoG > oUt1
parameter. The retransmission signal is then scaled using the following 4
parameters. The unit will display the first scaling parameter,
Rd1
, after
RtRN
is
selected.