background image

15

#

6.3  MODULE 3 - D

ISPLAY AND

P

ROGRAM

L

OCK

-

OUT

P

ARAMETERS

(

#

)

Module  3  is  the  programming  module  for  setting  the  Display  Lock-out

Parameters and the “Quick Programming Mode” Value Access Parameters. In the
Quick Programming mode, after the PROGRAM LOCKOUT PARAMETERS
and  before  the  Security  Code  (

#

),  a  Display  Intensity  Level  (

)

parameter is available when the security code is non-zero. It allows the display
intensity to be set to 1 of 16 levels (0-15).

ª

«

#

#

TIMER DISPLAY LOCK-OUT 

CYCLE COUNTER DISPLAY LOCK-OUT

ª

«

ª

«

#

ª

«

#

#

These displays can be programmed for 

or

#

. When a particular meter

function is not used, the Display Lock-out should be set to 

#

for that display.

Setpoint Values for SP1 thru SP4 can be programmed for 

 

, or 

#

.

'

and 

'

are only displayed when they apply to the Setpoint Action

(

#'

) programmed for that particular Setpoint. (See Module 6 for details.)

ª

«

#

'

SETPOINT 1 to 4 VALUE ACCESS ** (

''

= 1 thru 4)

ª

«

#

'

ª

«

#

'

PROGRAM LOCK-OUT PARAMETERS (VALUE ACCESS) 

“Full”  Programming  Mode  permits  all  parameters  to  be  viewed  and

modified. This programming mode can be locked with a Security Code and/or
a  User  Input.  When  locked,  and  the 

PAR

key  is  pressed,  the  meter  enters  a

Quick Programming Mode. In this mode, access to Setpoint Values, Timer &
Cycle Counter Start/Stop Values, and Time Setting for the Real-Time Clock can
be programmed for “Read”, “Enter”, or “Lock” defined as follows: 

Timer & Counter Start/Stop Values can be programmed for 

 

, or 

#

.

ª

«

#

#

TIMER & CYCLE COUNTER START/STOP VALUE ACCESS

ª

«

#

ª

«

#

ª

«

#

#

This  parameter  can  be  programmed  for 

 

or 

#

.  Selecting 

 

allows

setting or changing the RTC Time in Quick Programming mode.

ª

«

#

  #

to

Entry of a non-zero value will cause the 

#

prompt to appear when trying

to  access  the  “Full”  Programming  Mode.  Access  will  only  be  allowed  after
entering a matching security code or the universal unlock code of 

. With this

lock-out,  a  User  Input  would  not  have  to  be  used  for  the  Program  Lock-out
function. Note however, the Security Code lock-out is overridden when an User
Input, configured for Program Lock-out (

#

), is not active (See Chart.)

SECURITY CODE 

ª

«

#

PROGRAMMING MODE ACCESS

Throughout this bulletin, Programming Mode (without Quick in front) always

refers to “Full” Programming.

Immediate access

Full Programming

Not Active

#

0

No access

Quick Programming

Active

#

0

Immediate access

Full Programming

Not Active

#

not 0

After Quick Programming 
with correct Security
code entry

Quick Programming

Active

#

not 0

After Quick Programming 
with correct Security
code entry

Quick Programming

————

not 

#

not 0

Immediate access

Full Programming

————

not 

#

0

FULL PROGRAMMING

MODE ACCESS

MODE WHEN “PAR” 

KEY IS PRESSED

USER INPUT

STATE

USER INPUT

SELECTION

SECURITY

CODE

SELECTION

DESCRIPTION

Read

Visible, not changeable, in Quick Programming Mode

Lock

Not visible in Quick Programming Mode

Enter

Visible and changeable in Quick Programming Mode

DISPLAY

#

 

DISPLAY LOCK-OUT PARAMETERS

When  operating  in  the  Display  Mode,  the  meter  displays  can  be  viewed

consecutively by repeatedly pressing the 

DSP

key. The annunciators to the left

of the display indicate which display is currently shown. Timer (TMR), Cycle
Counter (CNT), or Date (DAT). The Time Display for the Real-Time Clock is
shown with no annunciator. Any of these displays can be locked from view with
the  DISPLAY  LOCK-OUT  parameters.  Using  these  parameters,  each  display
can be programmed for “Read” or “Lock” defined as follows:

DISPLAY

DESCRIPTION

Visible in Display Mode

#

Not visible in Display Mode

SELECTION

Read

Lock

** These parameters only appear if a Setpoint option card is installed.

 

= Setpoint Number 1 thru 4

PARAMETER MENU

PAXCK: REAL-TIME CLOCK DATE/TIME DISPLAY LOCK-OUT 

PAXCK: REAL-TIME CLOCK TIME SETTING ACCESS

Summary of Contents for PAX-1/8

Page 1: ...can be configured to trigger on the edge or level of the incoming pulse Internal jumpers are available to allow the selection for sinking inputs active low or sourcing inputs active high The front panel keys and three user inputs are programmable to perform various meter functions One of the functions includes exchanging parameter lists allowing for two separate listings of setpoint values timer s...

Page 2: ...ard Replacement Only SFPAX PAXRTC Accessories PAXCDC20 RS232 Serial Communications Output Card with Terminal Block Optional Plug In Cards PAXCDC30 PAXCDC2C DeviceNet Communications Card Terminal Block Extended RS232 Serial Communications Output Card with 9 Pin D Connector PAXCDC1C PAXCDC10 RS485 Serial Communications Output Card with Terminal Block PAXCDC PAXCDS40 Quad Setpoint Sourcing Open Colle...

Page 3: ... programmable user inputs Logic inputs configurable as Current Sinking active low or Current Sourcing active high through a single plug jumper Current Sinking active low VIL 0 9 V max 22K pull up to 12 VDC Current Sourcing active high VIH 3 6 V min 22K pull down Max Continuous Input 30 VDC Isolation To Timer Input Common Not isolated Response Time 10 msec 12 MEMORY Non volatile E2 PROM retains all...

Page 4: ...the SFPAX makes it easier to program the PAX meter and allows saving the PAX program in a PC file for future use On line help is available within the software A PAX serial plug in card is required to program the meter using the software SETPOINT CARDS PAXCDS The PAX and MPAX series has 4 available setpoint alarm output plug in cards Only one of these cards can be installed at a time Logic state of...

Page 5: ... The bezel should only be cleaned with a soft cloth and neutral soap product Do NOT use solvents Continuous exposure to direct sunlight may accelerate the aging process of the bezel Do not use tools of any kind screwdrivers pens pencils etc to operate the keypad of the meter PANEL CUT OUT 1 0 INSTALLING THE METER 2 0 SETTING THE JUMPERS To access the jumpers remove the meter base from the meter ca...

Page 6: ...methods must be followed to ensure compatibility in each application The type of the electrical noise source or coupling method into the meter may be different for various installations The meter becomes more immune to EMI with fewer I O connections Cable length routing and shield termination are very important and can mean the difference between a successful or troublesome installation Listed bel...

Page 7: ...t Switch or Isolated Transistor Current Sink Switch or Isolated Transistor Current Source Emitter Follower Current Source 4 1 POWER WIRING AC Power Terminal 1 VAC Terminal 2 VAC DC Power Terminal 1 VDC Terminal 2 VDC 4 3 USER INPUT WIRING Before connecting the wires the Timer Input logic jumper should be verified for proper position When the user input is configured for cycle count in module 4 the...

Page 8: ...ccession without a pause in between In these cases the meter employs a busy function As the meter begins to transmit data the RXD line RS232 is monitored to determine if the receiving device is busy The receiving device asserts that it is busy by setting the RXD line to a space condition logic 0 The meter then suspends transmission until the RXD line is released by the receiving device RS485 Commu...

Page 9: ...ost Real Time Clock Synchronization Figure 4 6 REAL TIME CLOCK WIRING PAXCK 5 0 REVIEWING THE FRONT BUTTONS AND DISPLAY Cycle counter and Real Time Clock displays are locked out in Factory Settings Factory setting for the F1 and F2 keys is NO mode Factory setting for the RST key is Reset Display Selects digit location in parameter values Reset Function key RST Decrement selected parameter value or...

Page 10: ... STEP PROGRAMMING INSTRUCTIONS OVERVIEW PROGRAMMING MENU DISPLAY MODE The meter normally operates in the Display Mode In this mode the meter displays can be viewed consecutively by pressing the DSP key The annunciators to the left of the display indicate which display is currently shown Timer TMR Cycle Counter CNT or Date DAT The Time Display for the Real Time Clock is shown with no annunciator An...

Page 11: ...Inhibit Level Active Time Start Time Stop Time Start Time Stop TIMER INPUT OPERATION 0 01 HR 0 001 HR 1 HR 0 1 HR 0 001 MIN HOURS 0 1 MIN 0 01 MIN MINUTES 1 MIN 0 01 SEC 0 001 SEC 1 SEC 0 1 SEC MAXIMUM DISPLAY DISPLAY RESOLUTION RANGE SELECTION SECONDS DAYS HOURS MINUTES 1 MIN 1 SEC 0 1 SEC 0 001 MIN HOURS MINUTES SECONDS 0 1 MIN 0 01 MIN HOURS MINUTES 1 MIN 0 01 SEC 0 001 SEC 1 SEC 0 1 SEC MAXIMU...

Page 12: ...n Keys Three rear terminal User Inputs are individually programmable to perform specific meter control functions While in the Display Mode the function is executed when the User Input transitions to the active state Refer to the User Input specifications for active state response times Certain User Input functions are disabled in Full Programming Mode User Inputs should be programmed while in the ...

Page 13: ... the meter continually resets the displays entered as in the sublist The sublist appears when the PAR key is pressed This function does not apply to the RTC Time or Date displays Cycle Counter Timer FACTORY DESCRIPTION DISPLAY ª ª MOMENTARY RESET Edge Triggered When activated momentary action the meter resets the displays entered as in the sublist Function does not apply to RTC Time or Date displa...

Page 14: ...t 3 Setpoint 2 Setpoint 1 FACTORY DESCRIPTION DISPLAY When activated momentary action the display intensity changes to the next intensity level of 4 The four levels correspond to Display Intensity Level settings of 0 3 8 15 The intensity level when changed via the User Input Function Key is not retained at power down unless Quick Programming or Full Programming mode is entered and exited The unit ...

Page 15: ...d after entering a matching security code or the universal unlock code of With this lock out a User Input would not have to be used for the Program Lock out function Note however the Security Code lock out is overridden when an User Input configured for Program Lock out is not active See Chart SECURITY CODE ª PROGRAMMING MODE ACCESS Throughout this bulletin Programming Mode without Quick in front ...

Page 16: ...op Value is not used CYCLE COUNTER STOP VALUE ª to CYCLE COUNTER RESET AT POWER UP The Cycle Counter can be programmed to Reset at each meter power up ª 6 5 MODULE 5 TIMER OPERATING MODES PARAMETER MENU This module can only be accessed if a Setpoint Card is installed Only the value parameters which apply to the selected mode will appear Interval Timing Edge Triggered Interval Timing Level Triggere...

Page 17: ...and User Input 1 terminals The Timer Input plug jumper and the User Input plug jumper must be set to opposite positions one SNK one SRC and the Input signal must be a current sinking type i e pulls input to common Parameter Settings for Predefined Timer Operating Modes MODULE 1 Timer Input Parameters MODULE 2 User Input Parameters MODULE 6 Setpoint Parameters Power up State Setpoint Annunciator Ou...

Page 18: ...ck Date Display the date value is entered in month day year format When assigned to the Real Time Clock Time Display the Setpoint value is always entered in format Hours Minutes with AM PM selection In Setpoint One shot mode See Daily On Occurrence the One shot Setpoint is enabled armed by scrolling the AM PM digit until the 2nd digit decimal point is lit SETPOINT OFF ª ª to Based on Setpoint Off ...

Page 19: ...ion This value is always entered in minutes seconds and hundredths of seconds format The maximum Time Out Value is 99 minutes 59 99 seconds ª TIMER COUNTER AUTO RESET When the Setpoint output activates or deactivates the meter automatically resets the Setpoint Assignment display Select if the Setpoint output should not cause the assigned display to reset Does not apply to manual activations or dea...

Page 20: ...rame size to 10 bits ª METER ADDRESS Enter the serial meter node address With a single meter an address is not needed and a value of zero can be used With multiple meters RS485 applications a unique 2 digit address number must be assigned to each meter to TST TSP CST CSP Timer Cnt Start Stop Values SO1 SO2 SO3 SO4 Setpoint Off Time Out Values SP1 SP2 SP3 SP4 Setpoint Values TIM RTC Time DAT RTC Da...

Page 21: ... 144500 2 45 PM Date Month Day Year mmddyy Ex 123101 December 31 2001 Day 1 Sunday through 7 Saturday EX 3 Tuesday Notes 1 Since the meter does not issue a reply to value change commands follow with a transmit value command for readback verification 2 The date and day must be set separately Transmitting Data From the Meter Data is transmitted from the meter in response to either a transmit command...

Page 22: ...nd output 2 inactive BYTE DESCRIPTION 1 12 12 byte data field 6 bytes for number up to 3 bytes for decimal points 13 CR Carriage return 14 LF Line feed 15 SP Space 3 16 CR Carriage return 3 17 LF Line feed 3 50 100 msec for 2 50 msec for Print P 50 100 msec for 2 50 msec for Transmit T 100 200 msec Write V 2 50 msec Reset R PROCESS TIME t2 COMMENT COMMAND COMMAND RESPONSE TIME The meter can only r...

Page 23: ...ing the parity bit is either even or odd This bit is used by the receiver to detect errors that may occur to an odd number of bits in the transmission However a single parity bit cannot detect errors that may occur to an even number of bits Given this limitation the parity bit is often ignored by the receiving device The PAX meter ignores the parity bit of incoming data and sets the parity bit to ...

Page 24: ... The oscillator is factory calibrated and optimized for 25 C ambient temperature operation Since the PAXCK is designed to operate over a wide temperature range and since the accuracy of a crystal oscillator varies with ambient temperature some drift in the RTC time may be observed over an extended period This is primarily seen in high or low temperature installations To compensate for the wide ope...

Page 25: ... Setpoint plug in card installation wiring Setpoint programming in Module 6 REAL TIME CLOCK NOT WORKING PROPERLY CHECK RTC plug in card installation RTC programming in Module 8 check for proper battery installation replace battery DO NOT ADJUST TRIM CAP ON RTC CARD SERIAL COMMUNICATIONS NOT WORKING CHECK Serial plug in card installation Serial wiring Serial settings in Module 7 host settings ERROR...

Page 26: ... START VALUE A CYCLE COUNTER STOP A B CYC CNTR RESET AT POWER UP CYCLE COUNTER START VALUE B DISPLAY PARAMETER USER SETTING FACTORY SETTING PARAMETER VALUE CHART Programmer ________________ Date ________ PAXCK Clock Timer Meter _____________ Security Code __________ SP2 TIME OUT VALUE ACCESS SP3 ON VALUE ACCESS RTC DATE DISPLAY LOCK OUT DISPLAY PARAMETER FACTORY SETTING USER SETTING TIMER RANGE TI...

Page 27: ...USER SETTING FACTORY SETTING Mon Fri Mon Fri Mon Fri Mon Fri SETPOINT ON B SETPOINT ACTION USER SETTING TIMER STOP Mon Fri DAILY OFF OCCURRENCE B Mon Fri DAILY OFF OCCURRENCE A Mon Fri DAILY ON OCCURRENCE B Mon Fri DAILY ON OCCURRENCE A SETPOINT ON VALUE B SETPOINT ON VALUE A SETPOINT ON A SETPOINT ASSIGNMENT Setpoint Alarm Parameters FACTORY SETTING USER SETTING FACTORY SETTING PARAMETER PAXCK Ap...

Page 28: ...alue Setpoint 1 Time out Value Setpoint Select Setpoint Assignment Setpoint Action Output Logic Setpoint On Setpoint Off Time out Value Daily On Occurrence Daily Off Occurrence Timer Stop Timer Counter Auto Reset Output Reset w Display Reset Setpoint Annunciator Power up State 2 Baud Rate Data Bit Parity Bit Meter Address 3 Set Time Factory Service Code Setpoint number Set Date Set Day Time Displa...

Reviews: