18
4.5.4 Configuration
• This section explains the Configuration page of the iServers’s Web interface.
• When connecting your device to the iServer, the Serial Communications parameters
must match, between the iServer and your serial device.
Figure 4.10 Configuration
4.5.4.A Serial Communication
Baud Rate:
The speed on the serial port and can be set from 300 to 115,200 bits/s
(default is 9600 bits/s.)
Data Bit:
Options are 7 or 8 (default is 7 bits.)
Parity:
Options are Odd, Even, and None (default is Odd.)
Stop Bits:
Options are 1 and 2 bits (default is 1 bit.)
Flow Control:
Options are Software Flow Control (Xon/Xoff), Hardware Flow Control
(CTS/RTS), and None (default is None.)
CONFIGURATION
CONFIGURATION
http://192.168.1.200
Address
Serial Communication
Remote Access (Tunneling)
Terminal Server
Main Menu
Save Reset
Baud Rate 9600
Data Bit 7 Bits
Parity odd
Stop Bits 1 bit
Flow Control none
Transciever RS-485
Modbus/TCP disable
End Character (Hex) 0D
Forward End Char enable
Timeout 0500 msecs
Serial Port Password disable
1234abcd
Connection Ctrl not used
Device No. 1
Connection Timeout 00100 msecs
TCP/UDP TCP
Server Type slave
Number of Connections 0
Local Port 02000
Remote Access disable
Remote IP Address 0.0.0.0
Remote Port 02000
A
B
C