OMEGA AIR WOS Installation And Operating Manual Download Page 3

WOS - Installation and operating manual 

 3 

Technical data 

 

Size 

Cold climate zone 

15°C 60%RH

 

Mild climate zone 

25°C 60%RH

 

Hot climate zone 

40°C 100%RH

 

 

WOS-4 

2,89 

2,43 

1,23 

Max oil adsorption[kg] 

4,82/170,22 

4,04/142,80 

2,05/72,32

 

Max FAD [Nm

3

/min]/[scfm] 

2,3 

3,4 

6,3 

Max condensate flow [l/h]

[1] 

WOS-8 

6,01 

5,04 

2,55 

Max oil adsorption[kg] 

10,01/353,55 

8,40/296,60 

4,25/150,21 

Max FAD [Nm

3

/min]/[scfm] 

4,7 

7,1 

13,1 

Max condensate flow [l/h]

[1]

 

WOS-20 

14,64 

12,28 

6,22 

Max oil adsorption[kg] 

24,40/861,73 

20,47/722,92 

10,37/366,12 

Max FAD [Nm

3

/min]/[scfm] 

11,4 

17,2 

32,0 

Max condensate flow [l/h]

[1]

 

WOS-35 

25,40 

21,31 

10,79 

Max oil adsorption[kg] 

42,34/1495,07 

35,52/1254,24 

17,99/635,21

 

Max FAD [Nm

3

/min]/[scfm] 

19,8 

29,8 

55,6 

Max condensate flow[l/h]

[1] 

[1]Max condensate volume per condensate drain single discharge is 0,250 ltr.

 

 

 

 

 

 

 

 

 

 

[2]Max. operating temperature is 65°C, but when temperature is over 45°C, performance may decrease. 

Materials 
 

Housing material 

HDPE 

Fittings 

Brass, Brass-zinc plated, Steel 

Filter material 

PP (polypropylene), Active carbon 

 

There is Technical datasheet available. For additional technical specification, contact 
manufacturer. 

 

 

 

WOS-4  WOS-8  WOS-20

 

WOS-35

 

Nr. of inlet connections 

Nr. of outlet 

connection 

Connection type 

Hosetail for pipe Ø int. 10 mm 

 

 

 

 

 

DIMENSIONS 

 

 

 

 

A [mm] 

416 

730 

820 

960 

B [mm] 

243 

343 

366 

386 

C [mm] 

411 

680 

940 

1137 

Operating temperature 

1,5 - 45°C (max. 65°C)

[2]

 

35 – 113°F (max. 149°F)

[2]

 

Operating media 

Condensate (air, water, oil); non-

aggressive; not suitable for emulsion

 

Residual oil content 

Less than 10ppm 

 

Summary of Contents for WOS

Page 1: ...ing manual WOS water oil separator Please read the following instructions carefully before installing separator unit into service Trouble free and safe operating of the unit can only be guaranteed if...

Page 2: ...oil 2 Depressurization chamber with air filter 3 First stage chamber 4 Condensate flow 5 Oil filter cartridge 6 Condensate flow water residual oil traces 7 Activated carbon filter cartridge final oil...

Page 3: ...99 635 21 Max FAD Nm 3 min scfm 19 8 29 8 55 6 Max condensate flow l h 1 1 Max condensate volume per condensate drain single discharge is 0 250 ltr 2 Max operating temperature is 65 C but when temper...

Page 4: ...d Installation and operating manual for those ad ons Maximum temperature and pressure for assembled system is the lowest of any individual part The medium used may not have any corrosive components th...

Page 5: ...malfunction caused by the use of ungenuine parts is not covered by Warranty or Product Liability Advanced dimensioning For advanced dimensioning please use following equations m Max oil adsorption g F...

Page 6: ...evice Make sure that white filter element is inserted in chamber 1 and carbon filter element is inserted in chamber 2 Fill the device with clean water Connect device to the system Outlet must be conne...

Page 7: ...with oil indicating test paper For test set please contact us or your local distributor Damaged components are to be replaced by new ones If a marked degree of damage is found the entire vessel is to...

Page 8: ...Installation and operating manual 8 OMEGA AIR d o o Ljubljana Cesta Dolomitskega odreda 10 SI 1000 Ljubljana Slovenia Tel 386 0 1 200 68 00 Fax 386 0 1 200 68 50 E mail info omega air si www omega air...

Reviews: