Troubleshooting

Maintenance

Problem

Possible Cause

Solution

Lamp not lighting.

Fuse breaking off.

Change fuse.

Poor connection between the plug 

and socket.

Repair or change socket.

Lamp has poor contact or worn 

down.

Tighten the connection or change 

a new lamp.

Lamp switch has poor contact.

Tighten the connection or change 

a new switch.

Condenser fan not running.

Condenser fan broken down.

Change condenser fan.

Thermostat is not set to the work 

position.

Revolve the thermostat knob to the 

operating position.

Thermostat terminal is not 

connected properly.

Reconnect the terminal.

The thermostat is worn down.

Change the thermostat.

Continuous operation.

Open the door too frequently.

Open the door as little as possible.

Too much storage.

Take out part of the storage.

Leakage of refrigerant.

Repair at a qualified service center.

Thermostat does not work 

properly.

Change the thermostat.

Unit noisy.

Cooler isn’t placed levelly.

Adjust the wheels.

Fixing screws of compressor or 

condenser are loose.

Tighten the screws.

Compressor or fan defective.

Ask help of professional to repair.

Caution: to ensure safety, the power plug must be pulled out before cleaning.

CLEANING OF THE UNIT

For cleaning the unit’s internal plastic parts, use a light solution of soap and water. Do not apply hard chemical 

detergents on the plastics as they may lose their brightness or even get deformed. The same applies to the 

external metallic surfaces. The use of hard chemicals could harm the painting of the metallic surfaces, thus 

affecting the sanitary protection of the unit.

Summary of Contents for RE-CN-305

Page 1: ...Revised 08 10 2023 Toll Free 1 800 465 0234 Fax 905 607 0234 Email service omcan com www omcan com Glass Door Refrigeration Models RE CN 305 215 145 Items 47460 47586 47563 Instruction Manual...

Page 2: ...f Contents Section Disclaimer General Information Safety and Warranty Technical Specifications Installation Operation Maintenance Troubleshooting Parts Breakdown Electrical Schematics Notes Warranty R...

Page 3: ...causados por fugas de agua La garant a por fugas de agua queda anulada si la temperatura ambiente supera los 75 F y el 55 de humedad relativa y el desag e del aparato no est conectado directamente a...

Page 4: ...e It s of the utmost importance to save these instructions for future reference Also save the original box and packaging for shipping the equipment if servicing or returning of the machine is required...

Page 5: ...tados sten dentro de la caja y no encuentre da os ocultos en la m quina Si el paquete ha sufrido un manejo de poco cuidado golpes o da os visible o oculto por favor anote en la factura antes de acepta...

Page 6: ...e defrosting process other than those recommended by the manufacturer 4 Do not damage the refrigerant circuit 5 Do not use electrical appliances inside the food storage compartments of the appliance u...

Page 7: ...e ignition due to incorrect parts The appliance is to be installed in accordance with the safety Notice Any person who is involved with working on or breaking into a refrigerant circuit should hold a...

Page 8: ...propriate fire extinguishing equipment shall be available on hand A dry chemical or CO2 fire extinguisher should be adjacent to the charging area No person carrying out work in relation to a REFRIGERA...

Page 9: ...ooler with a soft cloth with neutral soap or detergent RESIDENTIAL USERS vendor assumes no liability for parts or labor coverage for component failure or other damages resulting from installation in n...

Page 10: ...ental conditions To minimize the environmental effects on the unit s performance the Technical Specifications Model RE CN 305 RE CN 215 RE CN 145 Volume 285 L 10 1 cu ft 217 L 7 7 cu ft 140 L 4 9 cu f...

Page 11: ...f the shelves It is essential that the unit is levelled during operation so as to avoid possible ice formation on the evaporator s fins due to insufficient drainage of the condensates Tilt unit by 2 a...

Page 12: ...quently Open the door as little as possible Too much storage Take out part of the storage Leakage of refrigerant Repair at a qualified service center Thermostat does not work properly Change the therm...

Page 13: ...a voltage stabilizer Evaporator fan not running Fan switch defective Change the switch Fan switch terminal is not connected properly Connect the switch terminal or change a new terminal Notice the fo...

Page 14: ...14 Parts Breakdown Model RE CN 305 47460 Model RE CN 215 47586 Model RE CN 145 47563...

Page 15: ...for 47460 32 AN261 Top Fan Cover for 47460 10 AN248 Switch for 47460 23 Parts Breakdown Model RE CN 305 47460 Model RE CN 215 47586 Item No Description Position Item No Description Position Item No De...

Page 16: ...AN252 Glass Door for 47563 27 AN233 Compressor Cover Wire Steel for 47563 5 AN243 Compressor Plate for 47563 15 AN253 Front Cover of Bottom for 47563 28 AN234 Water Storage Box for 47563 6 AN244 Adju...

Page 17: ...17 Model RE CN 305 47460 Model RE CN 215 47586 Model RE CN 145 47563 Electrical Schematics...

Page 18: ..._______________ ________________________________________________________________________________________ ________________________________________________________________________________________ ______...

Page 19: ...ter online by visiting OMCAN PRODUCT WARRANTY REGISTRATION 3115 Pepper Mill Court Mississauga Ontario Canada L5L 4X5 https omcan com warranty registration or email to service omcan com Purchaser s Inf...

Page 20: ...relations avec nos clients et les fabricants de valeur Aujourd hui avec des partenaires en Am rique du Nord Europe Asie et Am rique du Sud nous travaillons continuellement am liorer et d velopper l e...

Reviews: