Page
2
from 3
3.
Connect the new battery with the same type (step
3
of the
installation procedure) and place it in the position
of the old one.
4.
Follow the step 5 of the installation procedure and power the
device..
total amount of the line’s power load
.
3.
It is sugested to check every month the indication LED for
battery charging, and by pushing instantly the TEST button to
check the emergency cirquit and the lamps. If the luminaire does
not light
4.
It is sugested to check every 6 months the minimum
autononous duration by disconnecting the mains power supply
.
Count the time that the lamps light and in case of less time than
the minimum autonomous duration the batteries must be
replaced. If the measured time is considerably less than the
minimum autonomous duration
The
replacement of the battery and the light source must be done
using parts of the same type, by the manufacturer or by a
competent person.
5.
t i
in battery recycling
points. Do not incinerate.
contact the installer.
contact the installer.
In case of inactive use for a period greater than 2 months,
disconnect the battery by pulling out the battery’s connector.
6.
I
s not allowed to discard batteries in to common trash
bins, they must be discarded only
Battery replacement
.
It can be done only by a competent person and after the mains
interruption
.
1.
Follow the step 2
o
f the installation
procedure.
2.
Disconnect the
cables
and remove the ol
d
battery.
3.
Connect the new battery with the same type
(step
3
of the installation procedure) and
place it in the position
of the old one.
4.
Follow the step 5 of the installation
procedure and power the device.
(*) Non Maintained operation: The luminaire lights its illumination
source, only in power supply’s failure.
Maintained operation: The luminaire lights its illumination source, when
it is powered by the mains power supply or not
.
923029009_09_012
NOTE:
LED= Light Emitting Diode
LABELING EXPLANATION:
X:
Self contained
0:
Non Maintained (*)
A:
Including test device
*90:
1.5 hour duration
18
0:
3
hours duration
The light source contained in this luminaire shall only be replaced by the manufacturer, or his agent, or a similar qualified person.
NOTE! The light source is non-user replaceable.
LED CHARACTERISTICS
Olympia Electronics S.A
.
50 °C max.
60 °C max.
Cable connection between main pcb and led module
20-25V
5.5W
2605163
2002163
Manufacturer
Model Number
Voltage Range
Connections
Nominal Power
Temperature (tc
)
GRL-
21
GRL-29
20-25V
2.8W
INDICATION LED STATUS (with the mains power supply connected
)
CHARGE
POWER
Disconnected battery
/
not charging
Charged battery
Normal operation mode
No mains power supply
Battery under charge
Indicator ON
Indicator Blinking
Indicator OFF