 “BAU LIGHT” SERIES SELF TESTING MAINTAINED EMERGENCY LUMINARIES

220-240V AC/50-60Hz

3 h

24 h

LED Charge, Battery Fault LED / Magnetic Test Contanct

IP54

3.6V/3Ah

4.6W / 4.8VA

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

5 to 40  C

o

up to 95% 

ABS/PC, PC

763gr.

220lm / 300lm

30

LED

 white 

4W / 4.3VA

3.6V/1.5Ah

150

6

lm / 1 0lm

734gr.

836gr.

807gr.

OPERATION TEMPERATURE RANGE

RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY  (Ni-Cd)

 

CHARGING TIME

INDICATIONS - CONTROLS

MINIMUM AUTONOMY DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

ILLUMINATION 

(230V AC / emergency) 

VEWING DISTANCE

ILLUMINATION SOURCE 

GENERAL

o

These  luminaires  are  used  indoors  (ta  40 C)  where 
emergency light is needed.
Each  luminaire  must  be  permanently  connected  to  mains 
power supply. In normal operation the illumination LEDs are 
lit  as  well  as  the  green  indicating  charge  LEDs  when  the 
battery is charging. In case of a mains power supply failure, 
the  luminaire    enters  in  emergency  mode  and  will  light 
automatically.  When the mains power supply is restored the 
device turns to normal operation.

INSTALLATION

To  install  the  luminaire  follow  the  installation  instructions  on 
page 3.

Battery Charging

The  battery  charging  procedure  is  controlled  by  the 
processor, this maintaining its best possible preservation, as 
it extends its duration.

Battery Cut-off

The  luminaire  enters  this  mode  when  the  mains  power 
supply  fails  and  battery  has  lost  all  its  energy.  During  this 
operation  the  luminaire  enters  the  idle  state  and  battery 
consumption is negligible, in order to be protected from deep 
discharge.

Manual Test

This test can be done by using the A-1900 card as described 
on page 2. The light source and the emergency circuit of the 
device are tested. The manual test can be conducted only if 
the mains power supply and the battery are connected.

Automatic Operational Test

This test includes all the operations of the manual test and is 
conducted  automatically  every  15  days.  In  order  to  be 
performed,  the  mains  power  supply  and  the  battery  should 
be connected. 

Automatic Autonomy Test

The Automatic Autonomy Test measures the device’s back up 
operation  and  emergency  duration.  This  test  is  conducted 
automatically  every  6  months.  In  order  to  be  performed,  the 
mains power supply and the battery should be connected and 
fully  charged.  If  the  battery  is  not  fully  charged,  the  test  is 
postponed  until  the  battery  is  completely  charged.  If  during 
this test, the autonomy is less than nominal, the battery fault 
led turns on continuously and the battery must be replaced. 

Emergency Operation

The autonomy duration of battery during emergency mode is 
at least 180 minutes. During emergency mode, a light source 
test is also performed.

Resetting Errors

Hold the A-1900 card in TEST position for 10 to 15 seconds in 
order  to  delete  all  LED  indicated  errors.  Then    the  device 
enters regular operation mode.

Connection to module (After request)

This  luminary  can  be  connected  to  any  of  the  following 
modules:  Remote  module,  address  module  and  fault  relay 
module. If you connect it to a module that supports inhibit or 
rest  mode,  you  should  know  that  these  commands  can  be 
cancelled  only  during  normal  mode  (e.g.  not  in  emergency). 
For installation refer to step 5 of the installation procedure on 
page 3.
Also  refer  to  the  user  manual  of  each  module  for  additional 
information.

Indication  LED  status  (with  connected  mains  power 
supply).

Charge (Green LED) 
On:
 

Good charge condition.

Blink: 

Battery is charging.

Οff: 

No battery (No charging current 

or disconnected battery).

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

3 years (1 year for the battery)

TECHNICAL CHARACTERISTICS

 

(for LED MODULE specifications see page 4)

358 x 85 x 88 mm

358 x 125 x 88 mm

358 x 85 x 88 mm

358 x 125 x 88 mm

*15m, **17m

15m 

15m 

*15m, **17m

GR-750/ST/HP/LL

GR-751/ST/LP/LL GR-752/ST/HP/HL GR-753/ST/LP/HL