background image

Battery  disposal .

I

s not allowed to discard batteries into common trash bins, they must be discarded only

Warnings

1. 

Service and maintence activities should be done only when the device is disconneted from the 

mains power supply and the battery.

2. During the installation the connections to the mains power supply and the battery must be 
done after all other connections are finished.
3.  The panel connection with the mains supply must be done via a10A external fuse or an 
automatic circuit breaker rated at 10A.

This fuse has to be a separate, labeled fuse.

4.  Always use cables with double insulation.
5.  The diameter of the cable must be at least 1mm.(

F

igure 9) 

6.  The inner insulation of each cable must not be cut more than 1cm (

F

igure 9) 

7.  The outer insulation must not be cut more than 1cm away from the internal insulation.
8.  The panel's internal fuse is T630mAL250V  with 5x20 dimensions.
9.  The batery fuse is a resetable fuse 

900m

A inside the panel.

When the connections to zones, sirens and other required outputs are finished then we must connect the mains 
power supply. In order to aid the installer during the initial installation, the panel offers a special configuration. This 
configuration is entered by setting MODE switch 1 to the ON position. After entering this mode the panel conducts 
an auto reset and the 'Power', 'Zone disable' and 'General disable' LEDs blink. The special functions that aid in 
working out various problems that might arise are:

If all the problems are corrected and the installation is operating normally then the MODE switch 1 must be placed in 
the  OFF position. The panel conducts a

n

 auto-reset and is ready for operation.

By using a special operation mode we can conduct a walk test of the system. To enter walk-test mode set the MODE switch 1 
to the ON position. The 'Power', 'Zone disable' and 'General disable' LEDs blink. If an alarm is manually given by either 
activating a BS-536 call point or by activating a smoke detector with smoke or simulated smoke particles the  corresponding 
Alarm LED of the zone  will light and the siren will sound for 2 seconds. Using this method we can test the operation of the 
zones.
 After finishing the walk test set the MODE switch 1 to the OFF position. The panel conducts an automatic reset and enters 
normal operation mode.

The optional function which is provided by the panel is the fire alarm devices paragraph 7.8 of

 EN 

54-2

 and delays to 

outputs (paragraph 7.11 of EN 54-2)

.

t i

 in battery 

recycling points.

Initial Installation

When  a  zone  has  an  open  circuit 

then  the  internal  buzzer  sounds  and  the  corresponding  LED  lights.  If  the 

problem is corrected then the buzzer is deactivated and the LED is 

turned off

.

When a zone has a short  circuit

 

then the internal buzzer sounds and the corresponding LED blinks. If the problem  

is corrected then the buzzer is deactivated and the LED is 

turned off

.

When a siren output has an open circuit

 

then the internal buzzer is activated and the corresponding   fault LED 

lights. If the problem is corrected then the buzzer is deactivated and the LED is 

turned off

.

When a siren output has a short circuit

 

then the internal buzzer sounds and the corresponding LED blinks. If the 

problem is corrected then the buzzer is deactivated and the LED

 is

 

turned off

.

When a battery fault exists

 

then the 'Batt fault' LED lights and the 'Power fault' LED blinks. If the problem is 

corrected then the LEDs are deactivated.

Walk - Testing

Optional Function of EN 54-2.

Design

Components  of  the  panels  have  been  selected  for  the  intended  purpose,  and  are  expected  to  operate  within  their 
specification when the environmental conditions outside the cabinet of the panel comply with class 3k5 of
EN 60721-3-3:1995.

Figure 8. 

Panels connection with

 

220-240V 

AC

.

220-240V AC

L

N

1 cm

Fuse: T630mAL250V (5x20)

1 cm

Figure 9.

Panels connection with

 

220-240V 

AC

 

PE

Page 8 from 

10

921163600_09_020

Summary of Contents for nsc BS-1632

Page 1: ...e AUX relay The required batteries for the panels are two A 920 12V 2 6Ah All functions and indications are according to European Norms EN 54 2 and EN 54 4 Top cover retaining screws Control Keyboard...

Page 2: ...respond to the siren outputs If a siren out has a short circuit or open circuit then the corresponding LED will blink If a siren is disabled the corresponding LED will light The next group of indicato...

Page 3: ...siren 1 and Siren2 LED lights for the siren 2 Using the keys 1 and 2 we can enable or disable the respective sirens The disabled sirens have a LED lighted The panel exits this mode if no key is press...

Page 4: ...d corresponding functions 921163600_09_020 Fault zone 1 Alarm zone 2 Alarm zone 1 Without Delay 30 second Delay 60 second Delay 90 Second Delay LED ON LED OFF LED OFF LED OFF LED OFF LED OFF LED ON LE...

Page 5: ...res with a cross section cable of 1 5mm Page 5 from 10 Figure 2 Connecting 4 detector bases to zone 1 Each base can accept BS 655 BS 660 or BS 657 detectors A remote indication LED BS 572 is connected...

Page 6: ...larm condition ATTENTION The relays are rated at 30VDC and 5A maximum No 230VAC signals can be connected to these relays Siren Sounder Connections Each panel offers 2 independent circuits for connecti...

Page 7: ...out by qualified personnel only Disconnect power before servicing Never insert or remove boards or componets with the power on During installation use grounded antistatic wrist band to protect this e...

Page 8: ...ble LEDs blink If an alarm is manually given by either activating a BS 536 call point or by activating a smoke detector with smoke or simulated smoke particles the corresponding Alarm LED of the zone...

Page 9: ...s output must be protected with a fuse of the same rating contacts are rated at 30VDC and 5A maximum Outputs Relays 325 x 240 x 85 mm 54 2 54 4 2 years Dimensions Weight Produced in accordance to Guar...

Page 10: ...LINDROS PIERIAS 60061 GREECE BS 1632 14 0848 CONVENTIONAL 4 ZONE FIRE ALARM PANEL INSTALL IN ACCORDANCE WITH PRODUCT MANUAL 921163600_08_019 GREEK 921163600_09_020 ENGLISH POWER SUPPLY 220 240V AC 50...

Reviews: