olympia electronics nsc BS-1632 Manual Download Page 3

Access  level 2:

 Includes all the functions that the user can do and an access code is required. The code is

 

"34”

, it is the same for all 

panels and can

 

not be changed. The functions that can be implemented using this code are the following:

Evacuate:

 

Gives evacuate signal to the panel. 

 

The user must enter the 

user code

 

( 34)  

and then the key

s

 

'4' 

and

 '4'

.

 Then the panel will go to alarm state.

 The sirens 

will 

sound and 

the internal buzzer 

also

Siren Silence:

 When an alarm is issued and we want to silence the sirens then we must enter the user code

( 34 )

 and then the keys 

'5' 

and

 '5'

. The sirens are silenced but the internal buzzer continues to sound.

  

 The panel remains 

in normal operation. A new alarm from another zone will resound the sirens.

 To  resound the sirens press again the same 

code.

Panel Reset:

 When an alarm or fault condition has occurred and we want to reset the panel we must enter the user code 

(34)

 and then the keys 

'5' 

and

  

'6’

. The panel lights all LEDs in sequence and then enters normal operation.

Zone enable/disable:

 If we want to disable the operation of specific zones then we must enter the user code

( 34 )

 and then the keys number 

'5' 

and

 

'4'

. The LED marked  'General disable' start to blink,  and if a zone is disabled the 

corresponding '

Fault

' LED lights to indicate this. Using the keys 1, 2, 3, 4, 5 and 6 we can enable or disable the respective 

zones. The disabled zones light the corresponding LED. The panel exits this mode if no key is pressed for more than 30 
seconds. The panel then conducts an automatic RESET and enters normal operation mode.

 D

isabled zones 

does not

 

give alarm or fault condition. 

If we have disabled zones then this is indicated with the indicators 'General disable' and the 

corresponding Disable LED zone and the buzzer sounds once every minute.

Siren enable/disable:

 If we want to disable the operation of specific sirens we must enter the code 

(34)

 and then the 

keys 

'6' 

and 

‘6’

. The LED marked 'General Test' start to blink, and if a siren is disabled Siren1 LED lights for siren 1 and 

Siren2 LED lights for the siren 2. Using the keys 1 and 2 we can enable or disable the respective sirens. The disabled 
sirens have a LED lighted. The panel exits this mode if no key is pressed for more than 30 seconds. The panel then 
conducts an automatic RESET   and enters normal operation mode. 

All disabled sirens are supplied with the proper 

voltage but the panel can not enable them or read their condition.

 If we have disabled sirens then this is indicated with the 

indicator 'General disable' and the buzzer sounds once every minute.

Delays ON/OFF:

 If we want to

 disable the delays of the outputs. We must 

enter the code 

(34)

 and then the keys 

'6' 

and 

‘4’

Then the delays will be disable, the LED 

marked 

“Delays ON” will turn off. To enable the delays we must press again 

the code.

Page 3 from 

10

921163600_09_020

Access  level 3:

These functions are implemented during the installation and need the technical code to be accessed. The technical code is 

 

"364"

, it is the same for all panels and can

 

not be changed. These functions can be implemented using the technical code 

are activation methods used for the relays and can be done only if the panel has not issued an alarm or fault condition. 
These functions are ancillary and not required by the EN 54-2.These methods of programming are:

 AUX RELAY programming:

 If we want to program the operation behaviour of the AUX RELAY we must enter the technical 

code 

( 364 )

 and then press the key 

'5'

. The 'General fault' and 'General alarm' LEDs start to blink. The Alarm 

zone 

LED

and the fault LED zone 

show the way the AUX RELAY .

 If the Alarm led of the zone is on then we have logic AND for the aux 

relay activation. If the fault led of the zone is on then we have logic OR for the aux activation.
For example if Alarm Zone 1 and 2 is on and Fault Zone 3 and 4 is on, then the relay will be activated when Z1 and Z2 is in 
alarm condition or Z3 or Z4 are in alarm condition
To change the state of each zone, press the corresponding number each time.

 In order to exit this programming mode and to store the settings in memory do not press any key for more than 30 seconds. 
This system will conduct an automatic RESET and will enter normal operation mode.

Summary of Contents for nsc BS-1632

Page 1: ...e AUX relay The required batteries for the panels are two A 920 12V 2 6Ah All functions and indications are according to European Norms EN 54 2 and EN 54 4 Top cover retaining screws Control Keyboard...

Page 2: ...respond to the siren outputs If a siren out has a short circuit or open circuit then the corresponding LED will blink If a siren is disabled the corresponding LED will light The next group of indicato...

Page 3: ...siren 1 and Siren2 LED lights for the siren 2 Using the keys 1 and 2 we can enable or disable the respective sirens The disabled sirens have a LED lighted The panel exits this mode if no key is press...

Page 4: ...d corresponding functions 921163600_09_020 Fault zone 1 Alarm zone 2 Alarm zone 1 Without Delay 30 second Delay 60 second Delay 90 Second Delay LED ON LED OFF LED OFF LED OFF LED OFF LED OFF LED ON LE...

Page 5: ...res with a cross section cable of 1 5mm Page 5 from 10 Figure 2 Connecting 4 detector bases to zone 1 Each base can accept BS 655 BS 660 or BS 657 detectors A remote indication LED BS 572 is connected...

Page 6: ...larm condition ATTENTION The relays are rated at 30VDC and 5A maximum No 230VAC signals can be connected to these relays Siren Sounder Connections Each panel offers 2 independent circuits for connecti...

Page 7: ...out by qualified personnel only Disconnect power before servicing Never insert or remove boards or componets with the power on During installation use grounded antistatic wrist band to protect this e...

Page 8: ...ble LEDs blink If an alarm is manually given by either activating a BS 536 call point or by activating a smoke detector with smoke or simulated smoke particles the corresponding Alarm LED of the zone...

Page 9: ...s output must be protected with a fuse of the same rating contacts are rated at 30VDC and 5A maximum Outputs Relays 325 x 240 x 85 mm 54 2 54 4 2 years Dimensions Weight Produced in accordance to Guar...

Page 10: ...LINDROS PIERIAS 60061 GREECE BS 1632 14 0848 CONVENTIONAL 4 ZONE FIRE ALARM PANEL INSTALL IN ACCORDANCE WITH PRODUCT MANUAL 921163600_08_019 GREEK 921163600_09_020 ENGLISH POWER SUPPLY 220 240V AC 50...

Reviews: