background image

922502058

_0

9

_00

4

The luminaire has the ability to be connected to GR-
6500 panel. In order to do so, the luminaire’s address 
has  to  be  unique  in  the  same  bus.  An  extra  leaflet 
including in the package with the addressing table.

2.

 The device must be connected to the mains power 

supply through a fuse  that is dependent on the total 
line’s  power load.

Connectors

3.

  In  case  of  battery  replacement,  this  must  be 

replaced  by  part  of  the  same  type,

  by  the 

manufacturer or 

by a competent person.                

Resetting errors

4.

 In case of inactive use for a period greater than 2 

months,  disconnect  the  battery  by  pulling  out  the 
battery’s connector. 

ΑΤΤΕΝΤΙΟΝ!

!!

5.

  The  control  gear  is  not  proof  against  supply 

voltage polarity reversal.

6.  It  is  not  allowed  to  discard  batteries  into 

common  trash  bins,  they  must  be  discarded 
only    in  battery  recycling  points.

 

Do  not 

incinerate.

CN11:

 Communication Port

 

Automatic Autonomy Test

1.

  Operations  for  installation,  maintainance  or 

testing must be done by authorized personnel only

.

The  Automatic  Autonomy  Test  is  conducted  every  6 
months and measures the device’s back up operation 
and  emergency  duration.  This  test  includes  all 
functions of the Manual Autonomy Test.

Push  the  test  button  for  more  than  10  seconds,  to 
delete all the LED indicated errors. Then  the device 
enters regular

 

operation mode.

Addressable Communication

CN10:

 Power connector

CN6 & CN7:

 Battery connector

CN5:

  Non user connector

CN7:

 Recess LED Port

CN9:

 Module Port

922502058

_0

9

_00

4

2

Installation methods

Wall mounting

Luminary disassembly

3

2

1

Insert the

cable grommet

Insert the

power cable

Insert the

power cable

After the desired installation follow the steps below

Automatic Operational Test

Manual

 

t

est

  for  emergency  operation  and  light 

source.

Manual 

A

utonom

y

 

T

est

A

 duration test can be conducted if the TEST button 

is pressed from 5 to 10 seconds. The luminar

y

 enters 

emergency mode, the charge LED is turned OFF and 
the  Battery  Fault  led  starts  to  blink.  The  test  is 
conducted until the battery is depleted.If at the end 
of  the  test  the  autonomy  is  low  then  the  Battery 
Fault LED will be ON. If the result of the test is good 
then  the  luminar

y

  enters  charging  mode  and  the 

Charge led starts to blink until the batteries are fully 
charged.

This test includes all the operations that provide the 
manual test and is conducted automatically every 15 
days.  In  order  to  be  performed,  the  mains  power 
supply and the battery should be connected.

The manual test can be conducted only if the mains 
power supply and the battery is connected

:

o

These  luminaries  are  used  indoors 

(

ta  40 C

)

  where 

emergency  light  is  needed.  Each  luminary  must  be 
permanently  connected  to  mains  power  supply.  In 
normal operation the led strip lights and the battery 
is  charging.  In    case    of    a    mains    power    supply 
failure    the  luminary  will  light  the  led  strip 
automatically  in  emergency  mode  (powered  by  its 
battery). When the mains  power  supply  is  restored 
the device turns to normal operation.

During the Test the lamp fault LED blinks. 

Insert the

power cable

Insert the

cable grommet

Ceiling mounting

1

922502058

_0

9

_00

4

1
1
1
1

Luminaire

Wall mounting accessories
Ceiling mounting accessories

Manual

Package contents

General

Hanging installation

1

L

B

N

A

Insert the signal

cable

Insert the

power cable

2

Luminary

 

assembly

Battery Connection

ON

1 2 3 4

Maintained operation

ON

1 2 3 4

Non-maintained operation

>5mm

:

1

2

Insert the

power cable

Insert the

cable grommet

N
L

Power Connection

Ν

 for neutral, 

L

 for live wire

A

A

B

B

Communication Connection

Pass the 2 signal cables and connect them 
on the A, B terminals minding the correct 
polarity. These cables are used to connect 
the luminaire to GR-6500 panel.

DS1

1h

ON

1 2 3 4

3h

(default position)

ON

1 2 3 4

8h

ON

1 2 3 4

Autonomy duration selection

The control of maintained or non maintained operation of the luminary is achieved through Switch 4 of DS1. 
For  maintained  operation,  switch  number  4  must  be  in  ON  position.  For  non-maintained  operation,  switch 
number 4 must be in OFF position.

Technical label installation

Two  additional  labels  are  included  in  the  package.  one  for  1  hour  duration  (60)  and  one  for  8  hour  duration 
(480). Depending on the selected duration, the installer must cover the default 3 hour (180) printing with one 
label that has the required duration. Please take notice of the orientation of the label.

Changing the operating mode

The  user  can  select  one  of  the  3  available  minimum  autonomy  durations  1  hour,  3  hours  and  8  hours.  The 
selection  must  be  done  while  the  luminaire  is  disconnected  from  AC  and  battery  supplies.  The  selection  is 
achieved through Switches 2 & 3 of DS1. Switch 1 is not used. 

Description

Indications

 

LED Status

BATT.

FAULT

(

yellow

)

LAMP
FAULT

(

red

)

CHARGE

(

green

)

Fully charged

Charging

Battery fault or
emergency mode

Operational test

Light source fault

Autonomy test

Duration fault

Note

:

Permanently

ON

Blink

Indifferent

Off

3

4

Set the luminaire’s address throught the dip switch.

Dip switch
position

5

Reviews: