922502058
_0
9
_00
4
The luminaire has the ability to be connected to GR-
6500 panel. In order to do so, the luminaire’s address
has to be unique in the same bus. An extra leaflet
including in the package with the addressing table.
2.
The device must be connected to the mains power
supply through a fuse that is dependent on the total
line’s power load.
Connectors
3.
In case of battery replacement, this must be
replaced by part of the same type,
by the
manufacturer or
by a competent person.
Resetting errors
4.
In case of inactive use for a period greater than 2
months, disconnect the battery by pulling out the
battery’s connector.
ΑΤΤΕΝΤΙΟΝ!
!!
5.
The control gear is not proof against supply
voltage polarity reversal.
6. It is not allowed to discard batteries into
common trash bins, they must be discarded
only in battery recycling points.
Do not
incinerate.
CN11:
Communication Port
Automatic Autonomy Test
1.
Operations for installation, maintainance or
testing must be done by authorized personnel only
.
The Automatic Autonomy Test is conducted every 6
months and measures the device’s back up operation
and emergency duration. This test includes all
functions of the Manual Autonomy Test.
Push the test button for more than 10 seconds, to
delete all the LED indicated errors. Then the device
enters regular
operation mode.
Addressable Communication
CN10:
Power connector
CN6 & CN7:
Battery connector
CN5:
Non user connector
CN7:
Recess LED Port
CN9:
Module Port
922502058
_0
9
_00
4
2
Installation methods
Wall mounting
Luminary disassembly
3
2
1
Insert the
cable grommet
Insert the
power cable
Insert the
power cable
After the desired installation follow the steps below
Automatic Operational Test
Manual
t
est
for emergency operation and light
source.
Manual
A
utonom
y
T
est
A
duration test can be conducted if the TEST button
is pressed from 5 to 10 seconds. The luminar
y
enters
emergency mode, the charge LED is turned OFF and
the Battery Fault led starts to blink. The test is
conducted until the battery is depleted.If at the end
of the test the autonomy is low then the Battery
Fault LED will be ON. If the result of the test is good
then the luminar
y
enters charging mode and the
Charge led starts to blink until the batteries are fully
charged.
This test includes all the operations that provide the
manual test and is conducted automatically every 15
days. In order to be performed, the mains power
supply and the battery should be connected.
The manual test can be conducted only if the mains
power supply and the battery is connected
:
o
These luminaries are used indoors
(
ta 40 C
)
where
emergency light is needed. Each luminary must be
permanently connected to mains power supply. In
normal operation the led strip lights and the battery
is charging. In case of a mains power supply
failure the luminary will light the led strip
automatically in emergency mode (powered by its
battery). When the mains power supply is restored
the device turns to normal operation.
During the Test the lamp fault LED blinks.
Insert the
power cable
Insert the
cable grommet
Ceiling mounting
1
922502058
_0
9
_00
4
1
1
1
1
Luminaire
Wall mounting accessories
Ceiling mounting accessories
Manual
Package contents
General
Hanging installation
1
L
B
N
A
Insert the signal
cable
Insert the
power cable
2
Luminary
assembly
Battery Connection
ON
1 2 3 4
Maintained operation
ON
1 2 3 4
Non-maintained operation
>5mm
:
1
2
Insert the
power cable
Insert the
cable grommet
N
L
Power Connection
Ν
for neutral,
L
for live wire
A
A
B
B
Communication Connection
Pass the 2 signal cables and connect them
on the A, B terminals minding the correct
polarity. These cables are used to connect
the luminaire to GR-6500 panel.
DS1
1h
ON
1 2 3 4
3h
(default position)
ON
1 2 3 4
8h
ON
1 2 3 4
Autonomy duration selection
The control of maintained or non maintained operation of the luminary is achieved through Switch 4 of DS1.
For maintained operation, switch number 4 must be in ON position. For non-maintained operation, switch
number 4 must be in OFF position.
Technical label installation
Two additional labels are included in the package. one for 1 hour duration (60) and one for 8 hour duration
(480). Depending on the selected duration, the installer must cover the default 3 hour (180) printing with one
label that has the required duration. Please take notice of the orientation of the label.
Changing the operating mode
The user can select one of the 3 available minimum autonomy durations 1 hour, 3 hours and 8 hours. The
selection must be done while the luminaire is disconnected from AC and battery supplies. The selection is
achieved through Switches 2 & 3 of DS1. Switch 1 is not used.
Description
Indications
LED Status
BATT.
FAULT
(
yellow
)
LAMP
FAULT
(
red
)
CHARGE
(
green
)
Fully charged
Charging
Battery fault or
emergency mode
Operational test
Light source fault
Autonomy test
Duration fault
Note
:
Permanently
ON
Blink
Indifferent
Off
3
4
Set the luminaire’s address throught the dip switch.
Dip switch
position
5