These  luminaries  are  used  indoors 

o

(

ta  40 C

)

  on  the  wall,  where 

emergency  light  is  needed.

 

Each 

luminary  must  be  permanently 
connected  to  mains  power  supply

 

In  normal  operation  the  battery  is 
charging.

 

In case of a mains power 

supply  failure  the  luminary    will 
light  the  led  strip  automatically  in 
emergency mode.

 

When the mains 

power supply is restored the device 
turns to normal operation.

Non  Maintained  /  maintained 
operation 

there  is  an  option  to 

select  the  non  maintained  or 
maintained  operation  by  placing 
the  jumper  to  the  appropriate 
position  according  to  figure  4  (see 
page 3)

.

Installation

T

y

o  install  the  luminar   follow  the 

installation instructions on pages

 

and 3.

ΑΤΤΕΝΤΙΟΝ

!!!

1.  Operations  for  installation, 
maintainance  or  testing  must  be 
done by authorized personnel only

.

2. 

The  device  must  be  connected 

to the mains power supply through 
a  fuse  dependent  by  the  total 
amount of the line’s  power load

.

3. 

It  is  suggested  to  check  every 

month  the  indication  LED  for 
battery  charging,  and  by  pushing 
the  TEST  button  to  check  the 
emergency  circuit.  The  led  strip 
should  light  as  long  as  the  TEST 
b u t t o n   i s   p r e s s e d   a n d   t h e  
indication  LED  for  battery  charging 
should  be  off.

  If  the  luminary 

doesn’t  work  as  described  above 
contact the installer.

4. 

It  is  suggested  to  check  every  6 

months  the  minimum  autononous 
duration  by  disconnecting  the 
mains  power  supply

.   

Count  the 

time that  the led strip lights and in 
case of less time than the nominal 
autonomy,  the  battery  must  be 
replaced.  If  the  measured  time  is 
considerably less than the nominal 
autonomy

 

  In 

contact  the  installer.

case  of  battery  replacement,  this 
must  be  replaced  by  part  of  the 
same type,

 by the manufacturer or 

by a competent person.
5. 

In  case  of  inactive  use  for  a 

period  greater  than  2  months, 
disconnect  the  battery  by  pulling 
out the battery’s connector.

  

6

.

  

I

s  not  allowed  to  discard 

t  i

batteries  in  to  common 
trash  bins,  they  must  be 
discarded  only 

in  battery 

recycling  points.

 

Do  not 

incinerate.

Test  Button-  Manual  Test  for 
emergency operation

The manual test can be conducted 
only if the mains power supply and 
the battery is connected

:

After  3  seconds,  the  luminary 
returns to normal operation. 

Indication LED status
Charge

On: 

Fully charged.

Off:

  No  battery  (No  charging 

current or disconnected battery).

Blink:

 Charging.

1
1
1
1

Luminaire

Wall mounting accessorie
Ceiling mounting accessorie

Manual

Package contents

Γενικά

1

922502050

_0

9

_00

8

2

922502050

_0

9

_00

8

Installation methods

Wall mounting

Luminary disassembly

Luminary

 

assembly

3

Battery replacement

4

3

5

2

1

Ενδεικτικά

1

2

N

L

Insert the

power cable

Insert the

power cable

Insert the

power cable

Insert the

power cable

1. 

Disassemble the luminary

.

2. 

Remove the battery connector and carefully remove the battery from its base

.

3. 

Install a new battery of the same type and rating

.

4. 

Assemble the luminary and power the device

.  

Α-2130

Accessorie for ceiling

 (

1m)

Α-2131

Accessorie for ceiling (0,5m)

Α-2132

Accessorie for ceiling (0,25m)

Α-2133

: Accessorie for wall mounting

Α-2136

: Accessorie for hanging installation

 (2,5m)

A-2520/PL

Suspended ceiling base 

>5mm

General

Insert the

cable grommet

Hanging installation

After the desired installation follow the steps below

Ceiling mounting

Maintained

(default)

Non

maintained

Battery

connection

Accessories for installation

(After request)

Insert the

cable grommet

Insert the

cable grommet

Insert the

power cable