Automatic Operational Test

This  test  includes  all  the  operations  that  are 
provided  in  manual  test  and  is  conducted 
automatically  every  15  days.  In  order  to  be 
performed,  the  mains  power  supply  and  the 
battery should be connected.

Automatic Autonomy Test

The  Automatic  Autonomy  Test  tests  the 
device’s  back  up  operation  and  emergency 
duration. This  test  is  conducted  automatically 
every 6 months. In order to be performed, the 

mains power supply should be connected and 
the  battery  must  be  fully  charged

If  the 

battery  is  not  fully  charged

the  test  is 

postponed

 

until  the  battery  is  completely 

charged.  If  during  this  test,  the  autonomy  is 
less  than  nominal  then  the  battery  fault  LED 
will  permanently  be  on  and  the  battery  must 
be replaced. 

Back Up Operation

The  autonomy  duration  of  battery  during 
emergency mode must be at least as the one 
stated 

in 

the 

list 

of 

the 

technical 

characteristics.  During  emergency  mode,  a 
light source test is also performed.

Resetting Errors

Hold the A-1900 card in TEST position for 10 
to  15  seconds  in  order  to  delete  all  LED 
indicated  errors.  Then    the  device  enters 
regular operation mode.

Connection to module

 

(After request)

This luminaire can be connected to any of the 
following  modules:  Remote  module,  address 
module

wireless  module  and  fault  relay 

module.  If  you  connect  it  to  a  module  that 
supports  inhibit  or  rest  mode,  you  should 
know that these commands can be cancelled 
only  during  normal  mode  (ie.  not  in 
emergency). For installation refer to step 3 of 
the istallation procedure in page 3.
Also  refer  to  the  user’s  manual  of  each 
module for additional information.

ΑΤΤΕΝΤΙΟΝ!

!!

1.  Operations  for  installation,  maintainance 
or  testing  must  be  done  by  authorized 
personnel  only

.

2. The  device  must  be  connected  to  the 
mains  power  supply  thr

o

u

gh

  a  fuse 

  that  is 

dependent  on  the  total  line’s   power  load.
3.  In  case  of  battery  or  lamp  replacement, 
these  must  be  replaced  by  parts  with  same 
type,  by  the  manufacturer  or  by  a  competent 
person.

                

4.  In  case  of  inactive  use  for  a  period 
greater  than  2  months,  disconnect  the 
battery  by  pulling  out  the  battery’s  connector. 
5

I

s  not  allowed  to  discard  batteries  in 

t  i

to  common  trash  bins,  they  must  be 
discarded  only 

 

in  battery  recycling 

points.  Do  not  incinerate.

Indication LED status (mains on)

Charge 

On:

 

 

Fully charged.

Οff:

 

 

No battery 

(

No charging current 

or disconnected battery

).

Blink:

 Charging.

Lamp Fault 

Οn:

 

Faulty LED.

Off:

 

 LED  OK.

Blink: 

Operational Test.

Battery Fault

 

Ο

ff

:

 

 Battery OK. 

ON

  (

With  Charge  LED  ON):

    Autonomy  or 

low  battery  problem 

(the  battery  must  be 

replaced).

Blink

 

(

With Charge LED Off): 

Autonomy test 

is performed

.

923493000

_0

9

_003

Page

 

2 from

 

7

Battery 

Fault

Lamp

Fault

Charge

Indicators

Summary of Contents for GR-490/WP

Page 1: ...can be conducted by holding the A 1900 card steadily for 5 to 10 seconds In order to be performed the mains power supply and the battery should be connected The luminaire enters emergency mode the cha...

Page 2: ...mote module address module wireless module and fault relay module If you connect it to a module that supports inhibit or rest mode you should know that these commands can be cancelled only during norm...

Page 3: ...cable through the hole in the grommet If required open another cutout cable entry hole and install the second supplied cable grommet Connect the cables as shown in the photograph Use the supplied self...

Page 4: ...o plastic brackets with the four screws figure 3 4 Mark the positions of the mounting holes on the brackets 5 Install the two supplied plaster board plugs by screwing them on the plaster board ceiling...

Page 5: ...ed in the plastic base 3 Place the luminaire on the desired mounting location and mark and drill these 4 holes Fit the supplied 4 plastic mounting plugs to these drilled holes on the mounting location...

Page 6: ...eset errors you must place the card in front of TEST by holding it for 10 to 15 seconds and removing it 923493000_09_003 Page 6 from 7 Battery replacement It can be done only by a competent person and...

Page 7: ...vided or has any repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing Products that have been damaged can be returned to the premises of our compa...

Reviews: