                         ‘’CLASSIC LIGHT’’ SERIES FOR SELF-TESTING MAINTAINED EMERGENCY LUMINAIRES

Bayblend FR3010, transparent  polycarbonate

TECHNICAL CHARACTERISTICS

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

POWER CONSUMPTION
BATTERIES (Ni-Cd)

CHARGING TIME

INDICATIONS - CONTROLS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

ILLUMINATION (MAINS / EMERGENCY)

ILLUMINATION SOURCE 

90min

24h

Charge, lamp fault, fault indication LED, TEST button

From overcharge and full discharge

IP 20

  150/300lm 

  6 power LED’s 

EN 60598-1, EN 60598-2-22,  ΕΝ 61547, EN 55015

0 to 40  C

o

Up to 95% 

3 years (1 year for the battery)

580gr.

262 x 100 x 70 mm

Thank  you  for  purchasing  this  product  of 
Olympia Electronics. A European manufacturer.

GENERAL

o

These  luminaires  are  used  indoors  (ta  40 C) 
where emergency light is needed.
Each luminaire must be permanently connected 
to mains power supply.
In  normal  operation  the  led  strip  lights  and  the 
battery is charging. In  case  of  a  mains  power  
supply  failure    the    luminaire    will    light  the  led 
strip    automatically  in  emergency  mode.    When 
the    mains    power    supply    is    restored  the 
device turns to normal operation.

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions on page 2.

Battery Cut-off

The  luminaire  enters  in  this  operation  when  the 
mains power supply fails and battery has lost its 
energy.  During  this  operation  the  luminaire 
enters the idle state and battery consumption is 
negligible,  in  order  to  be  protected  from  deep 
discharge.

Battery charging

The battery charging  is completely  controled. In 
this  case,  is  achieved  the  perfect    battery 
maintenance  ,  as  well  as  the  elongation  of  its 
duration.  When  the  battery  has  completely 
charged, it charges with a maintenance current.

Manual Test

The  manual  test  can  be  conducted  only  if  the 
main power supply and the battery is connected. 
By  pressing  the  test  button  briefly  an  operation 
test  is  initiated.  During  this  test  period  all 
indication LEDs are OFF.

Automatic test

This  test  includes  all  the  operations  that  provide 
the  manual  test  and  is  conducted  automatically 
every 15 days. In order to be performed, the main 
power  supply  and  the  battery  should  be 
connected. 

Automatic Autonomous Test

The  Automatic  autonomous  Test  is  conducted 
and measures the luminaire`s back up operation. 
This  test  is  conducted  automatically  every  six 
months.  In  order  to  be  performed,  the  main 
power  supply  and  the  battery  should  be 
connected (the battery should be charged). If the 
battery is not charged, the test is postponed until 
the  battery  is  completely  charged.  If  during  the 
Automatic  Autonomous  Test  the  luminaire’s 
duration  is  lower  than  the  named,  then  the 
battery must be replaced.

Back Up Operation

The  autonomous  duration  of  battery  during 
emergency mode is at least the one that is stated 
in  the  list  of  the  first  page.  During  emergency 
mode, a LED strip test is also performed.

Resetting Errors

Push the Test button for 5 seconds, to extinguish 
all  the  indicated  LED  errors.   Then  the  luminaire 
enters regular operation mode.

Indication  LED  status  (with  connected  mains 
power supply).
AC Charge 
On:  

              Good charge current.

Οff:    

            No battery (No charging current or 

disconnected battery).

Lamp fault

923119004_09_004

 

GR-119/6L/42V

35-45V AC

4.5VA

3.6V/1.5Ah