GENERAL

o

These  devices  are  used  indoors 

(

ta  40 C

)

  in 

places  where  emergency  luminaires  are 
needed.  The  luminaires

 

GR-490/WP  and 

GR-492/WP are suitable for corridors lighting 
and  the

 

GR-491/WP  and  GR-493/WP  for 

open  area  lighting

.

  Each  device  must  be 

permanently  connected  to  mains  power 
supply

.

  In  normal  operation  the  battery  is 

charging.  In  case    of  a  mains  power  supply 
failure,  the  device  enters  emergency  mode 
and the illumination LED turns on. When the  
mains    power    supply  is  restored  the  device 
turns to normal operation.

INSTALLATION

To install the luminaire follow the installation 
instructions 

ο

n page 3.

Battery Charging

The battery charging is completely controlled 
by  microprocessor  and  is  protected  from 
complete discharge and overcharge

.

Battery Cut-off

The  luminaire  enters  in  this  mode  when  the 
mains power supply fails

 

and battery has lost 

its  energy

During  this  mode  the  luminaire 

enters the idle state

 

and battery consumption 

is  negligible,  in  order  to  be  protected  from 
deep discharge.

Manual

 Test

This  test  can  be  done 

by  using  the

 

A-1900 

card

 

as described on page 6.

 The light source 

and  the  emergency  circuit  of  the  device  are 
tested.  The  manual  test  can  be  conducted 
only if the mains power supply and the battery 
are  connected.  During  this  test  period  the 
LAMP TEST LED will  blink. 

Manual Autonom

y

 Test

A duration test can be conducted by holding the 
A-1900  card  steadily  for  5  to  10  seconds.  In 
order to be performed, the mains power supply 
and  the  battery  should  be  connected.  The 
luminaire enters emergency mode, the charge 
LED  is  turned  OFF  and  the  Battery  Fault  led 
starts  to  blink. The  test  is  performed  until  the 
battery  is  fully  discharged.If  at  the  end  of  the 
test the autonomy is low then the Battery Fault 
LED will be ON. If the result of the test is good 
then  the  luminaire  enters  charging  mode  and 
the Charge led starts to blink until the batteries 
are fully charged. 

WATERPROOF SELF TESTING N

ON

-M

AINTAINED

 EMERGENCY CEILING MOUNTED 

LUMINAIRE

S

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL

EXTERNAL DIMENSIONS
WEIGHT
GUARANTEE

OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY

 (

Ni-Mh

)

CHARGE TIME

INDICATIONS 

BATTERY PROTECTION

MINIMUM DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

LIGHT SOURCE

24 hours

LED

 

Charge

 

, Lamp Fault LED, Battery Fault LED / Magnetic Test Contanct

Deep discharge and overcharge protection

IP65

1

 

white

 

power LED

o

5

 to 40  C

Up to 95% 

3 years

 (1 

year for the battery

)

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

3 hour

    280lm 

  140lm 

576gr.

220-240V AC

 

/ 50-60Hz

TECHNICAL CHARACTERISTICS

 

(for LED MODULE specifications see page 7)

 GR-49

0

/WP

 GR-491/WP

 GR-492/WP

 GR-493/WP

ABS/PC

PC

158 x 158 x 60,4mm (without decorative bezel) - 195 x 195 x 60,4 (with decorative bezel)

Thank you for your trust in our products  

Olympia Electronics - European manufacturer

4.8V/1.2

 

Ah

3.9W / 4.4VA

1

.

5

 hour

Summary of Contents for GR-490/WP

Page 1: ...can be conducted by holding the A 1900 card steadily for 5 to 10 seconds In order to be performed the mains power supply and the battery should be connected The luminaire enters emergency mode the cha...

Page 2: ...mote module address module wireless module and fault relay module If you connect it to a module that supports inhibit or rest mode you should know that these commands can be cancelled only during norm...

Page 3: ...cable through the hole in the grommet If required open another cutout cable entry hole and install the second supplied cable grommet Connect the cables as shown in the photograph Use the supplied self...

Page 4: ...o plastic brackets with the four screws figure 3 4 Mark the positions of the mounting holes on the brackets 5 Install the two supplied plaster board plugs by screwing them on the plaster board ceiling...

Page 5: ...ed in the plastic base 3 Place the luminaire on the desired mounting location and mark and drill these 4 holes Fit the supplied 4 plastic mounting plugs to these drilled holes on the mounting location...

Page 6: ...eset errors you must place the card in front of TEST by holding it for 10 to 15 seconds and removing it 923493000_09_003 Page 6 from 7 Battery replacement It can be done only by a competent person and...

Page 7: ...vided or has any repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing Products that have been damaged can be returned to the premises of our compa...

Reviews: