‘’CLASSIC LIGHT’’ SERIES FOR SELF-TESTING MAINTAINED EMERGENCY LUMINAIRES
Bayblend FR3010, transparent polycarbonate
TECHNICAL CHARACTERISTICS
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
POWER CONSUMPTION
BATTERIES (Ni-Cd)
CHARGING TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
ILLUMINATION (MAINS / EMERGENCY)
ILLUMINATION SOURCE
90min
24h
Charge, lamp fault, fault indication LED, TEST button
From overcharge and full discharge
IP 20
150/300lm
6 power LED’s
EN 60598-1, EN 60598-2-22, ΕΝ 61547, EN 55015
0 to 40 C
o
Up to 95%
3 years (1 year for the battery)
580gr.
262 x 100 x 70 mm
Thank you for purchasing this product of
Olympia Electronics. A European manufacturer.
GENERAL
o
These luminaires are used indoors (ta 40 C)
where emergency light is needed.
Each luminaire must be permanently connected
to mains power supply.
In normal operation the led strip lights and the
battery is charging. In case of a mains power
supply failure the luminaire will light the led
strip automatically in emergency mode. When
the mains power supply is restored the
device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 2.
Battery Cut-off
The luminaire enters in this operation when the
mains power supply fails and battery has lost its
energy. During this operation the luminaire
enters the idle state and battery consumption is
negligible, in order to be protected from deep
discharge.
Battery charging
The battery charging is completely controled. In
this case, is achieved the perfect battery
maintenance , as well as the elongation of its
duration. When the battery has completely
charged, it charges with a maintenance current.
Manual Test
The manual test can be conducted only if the
main power supply and the battery is connected.
By pressing the test button briefly an operation
test is initiated. During this test period all
indication LEDs are OFF.
Automatic test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the main
power supply and the battery should be
connected.
Automatic Autonomous Test
The Automatic autonomous Test is conducted
and measures the luminaire`s back up operation.
This test is conducted automatically every six
months. In order to be performed, the main
power supply and the battery should be
connected (the battery should be charged). If the
battery is not charged, the test is postponed until
the battery is completely charged. If during the
Automatic Autonomous Test the luminaire’s
duration is lower than the named, then the
battery must be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is stated
in the list of the first page. During emergency
mode, a LED strip test is also performed.
Resetting Errors
Push the Test button for 5 seconds, to extinguish
all the indicated LED errors. Then the luminaire
enters regular operation mode.
Indication LED status (with connected mains
power supply).
AC Charge
On:
Good charge current.
Οff:
No battery (No charging current or
disconnected battery).
Lamp fault
923119004_09_004
GR-119/6L/42V
35-45V AC
4.5VA
3.6V/1.5Ah