energy
.
During this mode the device enters in idle
state
and battery consumption is negligible, in
order to be protected from deep discharge.
This test can be done by pushing the test button.
The light source and the emergency circuit of the
device are monitored. The manual test can be
conducted only if the main power supply and the
battery are connected. During this test period all
indication LEDs are OFF.
This test monitors the device’s back up operation
and emergency duration. The BATTERY FAULT
LED blinks during the test, indicating this
process to the user. This test is conducted
automatically every six months
.
In order to be
performed, the mains power supply should be
connected and the battery must be fully charged
.
If the battery is not fully charged
,
the test is
postponed
until the battery is completely
charged. If during this test, the autonomy is less
than the nominal then the battery fault led turns
on continuously indicating that the battery must
be replaced.
Manual
Test
Automatic Operational Test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
mains power supply and the battery should be
connected.
Automatic Autonomous Test
The luminaire has the ability to be connected to
GR-6500 panel. In order to do so, the
luminaire’s address has to be unique in the
same bus. For more details see page 3
(installation instruction).
The autonomous duration of battery during
emergency mode is at least the one that is stated
in the list of the technical characteristics. During
emergency mode, a light source test is also
performed.
Resetting Errors
Test Switch
Push the Test button for >10 seconds, to delete
all the indicated LED errors. Then the device
enters regular
operation mode.
Pressing the test switch less than 5 seconds will
initiate a light source test (last for 3 secs).
Back Up Operation
If the test switch is pressed for more than 10
seconds, the device will be reset (delete all
Addressable communication
ΑΤΤΕΝΤΙΟΝ
!!!
1. Operations for installation or maintainance
must be done by authorized personnel only
.
2.
The device must be connected to the mains
power supply through a fuse dependent by the
total amount of the line’s power load
.
errors).
3. The replacement of the battery and the light
source must be done using parts of the same
type, by the manufacturer or by a competent
person.
4
.
In case of inactive use for a period greater
than 2 months, disconnect the battery by pulling
out the battery’s connector.
5
.
I
s not allowed to discard batteries into
t i
common trash bins, they must be
discarded only
in battery recycling
points. Do not incinerate.
LABELING EXPLANATION:
A:
Including test device
Maintained operation: The luminaire lights its
illumination source, when it is powered by the
mains power supply or not
.
X:
Self contained
CN1:
Power supply & communication signals
(*)
Non Maintained operation: The luminaire turns
on illumination source,
only in case of power
supply failure.
CN2:
Non user connector
F:
Automatic test gear complying with IEC 61347-
2-7 denoted EL-T
CN5:
Battery connector
NOTE:
LED= Light Emitting Diode
18
0:
3
hour duration
0:
Non maintained (*)
Connectors:
B:
Including remote test mode
C:
Including inhibiting mode
CN3:
Non user connector
Page
2 from
8
Status of LEDs
LEDs
Description of indication
CHARGE : Battery charging, : battery charged, : disconnected battery
LAMP FAULT : Operation check, : lamp fault, : normal operation
BATT. FAULT : Autonomy test, : autonomy fault, : normal operation
Note : Blinking, : constantly on, : off