GENERAL
o
These luminaires are used indoors
(
ta 40 C
)
where emergency light is needed.
Each luminaire must be permanently
connected to mains power supply
.
Iin normal operation the battery is charging
and the 2 yellow LED’s light in each side of
the screen
.
In case of a mains power supply failure
t h e l u m i n a i r e w i l l l i g h t t h e l e d s t r i p
automatically in emergency mode. When
the mains power supply is restored the
device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 3.
ΑΤΤΕΝΤΙΟΝ
!!!
1. Operations for installation, maintainance
or testing must be done by authorized
personnel only
.
2.
The device must be connected to the
m a i n s p o w e r s u p p l y t h r o u g h a f u s e
dependent by the total amount of the line’s
power load
.
3.
It is suggested to check every month the
indication LED for battery charging, and by
pushing the TEST button to check the
emergency circuit. The lamp should light as
long as the TEST button is pressed
4.
It is suggested to check every 6 months
the minimum autononous duration by
disconnecting the mains power supply
.
Count
the time that the led strip lights and in case
of less time than the minimum autonomous
duration the battery must be replaced. If the
measured time is considerably less than the
minimum autonomous duration
In case of battery or led strip
replacement, these must be replaced by
parts of the same type, by the manufacturer
or by a competent person.
t i
in battery recycling
points.
. In the
opposite condition contact the installer.
contact the
installer.
5.
In case of inactive use for a period greater
than 2 months, disconnect the battery by
pulling out the battery’s connector.
6.
I
s not allowed to discard batteries in
to common trash bins, they must be
discarded only
923393000_09_008
Page
1
from
4
NON MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LEDs
ABS/PC, PC
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES
(
Ni-Cd
)
CHARGING TIME
INDICATIONS
-
CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
ILLUMINATION SOURCE
24h
Battery charging LED
,
TEST button
From overcharge and deep discharge
IP40
5 to 40 C
o
Up to 95%
3 years
(1
year for the battery
)
350
x 134 x 60 mm (CRV 362 x 134 x 90 mm)
GR-393/L
GR-391/L
220-240V AC/50-60Hz
3.6V/3Ah
3.6V/1.5Ah
4W/ 4.3VA
2.5W/ 3VA
180 min
90 min
270lm
2X16 LED
940gr (CRV 1020gr)
1030gr (CRV 1110gr)
EN 60598-1, EN 60598-2-22
, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
TECHNICAL CHARACTERISTICS
(
for LED MODULE Specs. see page 4
)
Congratulations for your selection to buy this product.
Olympia Electronics - European manufacturers
.