Date
22/4/2021
Document number
921100400_09_005
Page
5 of 71
5 / 71
1 General Information
Thank you for your trust in our products
Olympia Electronics
–
European manufacturer
1.1
General description
The
BSR-100X
series of
Analogue Addressable Fire Alarm Panels
consists of 3 models (1, 2 and 4
loop connections), named
BSR-1001
,
BSR-1002
and
BSR-1004
respectively, all sharing the same control
interface, functionality and indications. The accompanying software application for Windows PC,
BSR-
100X
provides utilities for calculating installation parameters, configuring the control panel and keeping an
event log record.
All BSR-100X models include 4 outputs for conventional sirens, an alarm relay, a fault relay and a
programmable auxiliary relay. Two 12V lead acid (Pb) batteries are required in each control panel. The
supported battery capacity is 7Ah, 9Ah, 12Ah or 15Ah, which must be calculated in accordance with the
size of the installation (number of devices) and the required emergency duration (during mains
interruption). It is always
recommended to use the “
Battery Calculator
”
tool (included in BSR-100X
software app) to calculate the required battery capacity according to your installation needs.
The available loop output connections are: 1 for BSR-1001, 2 for BSR-1002 and 4 for BSR-1004. Each
loop output connection can support up to 150 addressable units (smoke and heat detectors, addressable
sirens, manual fire call points, etc.).
The “
Loop Calculator
” tool (included in BSR
-100X software app) shall
be used for cable selection according to your installation size.
All features and indications are in accordance with European standards
ΕΝ
54-2 and
ΕΝ
54-4.
The BSR-100X series Analogue Addressable Fire Alarm Panels is ideal for medium to large scale facilities
such as department stores, hotels and factories.
An extended variety of settings and functionalities for controlling the fire alarm system (such as sirens,
output relays and other) under certain events (by zone or task), is available via the software BSR-100x
(for Windows PC). The communication between PC and control panel is via a USB cable.
The repeater BSR-1000 along with the BSR-100x fire detection panel series, allow the user to execute
basic functions for controlling, monitoring as well as reading the event log of the system. All, through the
built-in keypad and the LCD graphic display.
1.2
Safety
To ensure proper use of a device all accompanying documents must be read carefully.
This product must be installed, commissioned and maintained by
trained technician personnel
in
accordance with:
•
The regional regulations for the installation of electrical appliances in buildings
•
The regional Fire Safety regulations
•
Manufacturer's instructions
-The device mains power supply is rated at 220-240V AC / 50-60Hz, being a
Class
I
product (the
corresponding terminal contact with the “Protective Earth”
marking, inside the device, must be
connected to the
building’s
ground to ensure proper function and safety).
- Being a type B equipment (permanently connected to mains) the mains power supply to the device must
be connected to the existing
building’s
electrical installation, with its own separate power line and circuit-
breaker rated at 16A, labeled with
"Fire Detection System - Do not switch off"
.